Table 22 — Fan Performance — 48PGF28 — Horizontal Supply and Return Units

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

6,500

 

E

799

 

2.58

E

833

 

2.79

E

872

 

3.05

 

914

 

3.36

F

958

 

3.71

7,000

 

856

 

3.19

 

887

 

3.41

F

921

 

3.67

F

958

 

3.98

999

 

4.33

 

 

 

 

 

 

 

 

 

7,500

 

F

913

 

3.89

F

941

 

4.12

972

 

4.39

 

1006

 

4.69

 

1042

 

5.04

 

 

 

 

 

 

 

 

 

8,000

 

971

 

4.69

 

996

 

4.93

 

1024

 

5.20

 

1055

 

5.51

G

1088

 

5.86

 

 

 

 

 

 

 

 

 

 

8,500

 

 

1029

 

5.60

 

1052

 

5.85

G

1078

 

6.12

G

1106

 

6.44

 

1136

 

6.78

9,000

 

G

1087

 

6.62

G

1108

 

6.87

 

1132

 

7.16

 

1158

 

7.47

 

1185

 

7.82

9,500

 

 

1145

 

7.75

 

1165

 

8.02

H

1187

 

8.31

H

1211

 

8.63

H

1236

 

8.99

10,000

 

H

1203

 

9.01

H

1222

 

9.29

1243

 

9.59

1265

 

9.92

 

1288

 

10.28

10,500

 

1261

 

10.40

1279

 

10.69

 

1299

 

11.00

 

1319

 

11.34

 

1341

 

11.70

11,000

 

 

1320

 

11.93

 

1337

 

12.23

 

1355

 

12.55

 

1374

 

12.89

 

1394

 

13.26

11,500

 

 

1378

 

13.61

 

 

 

 

 

 

 

 

12,000

 

 

 

 

 

 

 

 

 

 

 

12,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

 

Rpm

 

Bhp

6,500

 

F

1005

 

4.12

 

1052

 

4.57

 

1100

 

5.06

G

1148

 

5.60

 

1195

 

6.17

7,000

 

 

1041

 

4.72

G

1084

 

5.16

G

1128

 

5.64

1172

 

6.17

H

1217

 

6.74

 

 

 

 

 

 

 

 

7,500

 

G

1080

 

5.43

1119

 

5.86

 

1160

 

6.33

 

1201

 

6.84

1242

 

7.40

8,000

 

1122

 

6.24

 

1158

 

6.66

 

1195

 

7.13

H

1233

 

7.63

 

1272

 

8.17

 

 

 

 

 

 

 

 

 

 

8,500

 

 

1167

 

7.16

 

1200

 

7.58

H

1234

 

8.04

 

1269

 

8.53

 

1304

 

9.06

9,000

 

H

1214

 

8.21

H

1244

 

8.62

 

1275

 

9.07

 

1308

 

9.56

 

1340

 

10.08

9,500

 

1262

 

9.37

 

1290

 

9.78

 

1319

 

10.23

 

1349

 

10.71

 

1379

 

11.23

10,000

 

 

1312

 

10.66

 

1338

 

11.08

 

1365

 

11.52

 

1392

 

12.00

 

 

10,500

 

 

1363

 

12.09

 

1387

 

12.51

 

 

 

 

 

 

11,000

 

 

 

 

 

 

 

 

 

 

 

11,500

 

 

 

 

 

 

 

 

 

 

 

12,000

 

 

 

 

 

 

 

 

 

 

 

12,500

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bhp —

Brake Horsepower Input to Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boldface indicates field-supplied motor/drive required.

NOTES:

1.Motor drive ranges:

(E)Low Range: 687-873 rpm, 5.75 bhp

(F)Mid-Low Range: 805-1007 rpm, 5.75 bhp

(G)Mid-High Range: 941-1176 rpm, 8.63 bhp

(H)High Range: 1014-1297 rpm, 11.50 bhp

All other rpms require field-supplied motor or drive.

2. See below for general fan performance notes.

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

1.Static pressure losses (i.e., economizer, electric heat, etc.) must be added to external static pressure before entering Fan Performance table.

2.Interpolation is permissible. Do not extrapolate.

3.Fan performance is based on wet coils, clean filters, and casing losses. See Accessory/FIOP Static Pressure information on page 39.

4.Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using the fan motors up to the bhp rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

5.Use of a field-supplied motor may affect wire size. Recalculate the unit power supply MCA and MOCP if required. Contact the local Carrier repre- sentative for details.

6.Use the following formula to calculate Input Watts: Input Watts = Bhp x (746/motor eff.)