Table 14 — Fan Performance — 48PGD20 — Horizontal Supply and Return Units
AIRFLOW |
|
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
|
| ||||||
| 0.2 |
|
| 0.4 |
|
|
| 0.6 |
|
| 0.8 |
|
| 1.0 |
| ||||||
(Cfm) |
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| Rpm |
| Bhp | |
5000 |
| 862 |
| 2.65 |
| 917 |
| 2.93 | F | 969 |
| 3.21 | F | 1019 |
| 3.17 | F | 1066 |
| 3.52 |
|
5500 | F | 937 |
| 3.26 | F | 988 |
| 3.56 | 1036 |
| 3.53 | 1083 |
| 3.90 | G | 1127 |
| 4.28 |
| ||
6000 | 1013 |
| 3.58 |
| 1060 |
| 3.96 |
| 1105 |
| 4.35 |
| 1149 |
| 4.75 | 1191 |
| 5.16 |
| ||
6500 |
| 1089 |
| 4.48 | G | 1133 |
| 4.89 | G | 1175 |
| 5.31 | G | 1216 |
| 5.73 | H | 1256 |
| 6.17 |
|
7000 | G | 1166 |
| 5.52 | H | 1207 |
| 5.96 | H | 1247 |
| 6.41 | H | 1285 |
| 6.86 | 1323 |
| 7.32 |
| |
7500 | H | 1243 |
| 6.71 | 1282 |
| 7.18 | 1319 |
| 7.66 |
| 1355 |
| 8.14 |
| 1391 |
| 8.63 |
| ||
8000 | 1320 |
| 8.07 |
| 1356 |
| 8.57 |
| 1392 |
| 9.08 |
| — |
| — |
| — |
| — | ||
8500 |
| 1398 |
| 9.60 |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — | |
9000 |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
AIRFLOW |
|
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) |
|
|
|
|
|
|
| ||||||
| 1.2 |
|
| 1.4 |
|
|
| 1.6 |
|
| 1.8 |
|
| 2.0 |
| ||||||
(Cfm) |
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| Rpm |
| Bhp |
| Rpm |
| Bhp | |
5000 | F | 1112 |
| 3.88 | F | 1156 |
| 4.25 | G | 1199 |
| 4.63 | G | 1240 |
| 5.02 | G | 1280 |
| 5.42 |
|
5500 | G | 1171 |
| 4.67 | G | 1212 |
| 5.06 | 1253 |
| 5.47 | H | 1292 |
| 5.88 | H | 1331 |
| 6.30 |
| |
6000 | 1232 |
| 5.57 | H | 1271 |
| 6.00 | H | 1310 |
| 6.43 |
| 1348 |
| 6.87 |
| 1384 |
| 7.31 |
| |
6500 | H | 1295 |
| 6.61 | 1333 |
| 7.06 |
| 1369 |
| 7.52 |
| — |
| — |
| — |
| — | ||
|
|
|
|
|
|
|
|
| |||||||||||||
7000 |
| 1360 |
| 7.80 |
| 1396 |
| 8.27 |
| — |
| — |
| — |
| — |
| — |
| — | |
7500 |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — | |
8000 |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — | |
8500 |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — | |
9000 |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
| — |
|
LEGEND
Bhp — Brake Horsepower Input to Fan
Boldface indicates
NOTES:
1.Motor drive ranges:
(E)Low Range: Not Used
(F)
(G)
(H)High Range:
All other rpms require
2. See page 36 for general fan performance notes.
28