Carrier PTV, 50PTH specifications Blower Performance Data

Models: 50PTH PTV

1 64
Download 64 pages 3.31 Kb
Page 28
Image 28
Table 13 — Blower Performance Data

Table 13 — Blower Performance Data

50PT

MAX ESP

FAN

TAP

COOLING MODE (cfm)

DEHUMIDIFICATION MODE (cfm)

HEATING MODE (cfm)

MOTOR

 

 

 

 

 

 

 

 

 

UNIT SIZE

(in. wg)

SETTING

Stage 1

Stage 2

Fan

Stage 1

Stage 2

Fan

Stage 1

Stage 2

Fan

 

 

(hp)

 

 

 

 

 

 

 

 

 

 

 

 

 

4

810

950

475

630

740

475

920

1060

475

026

0.50

1/2

3

725

850

425

560

660

425

825

950

425

2

620

730

370

490

570

370

710

820

370

 

 

 

 

 

 

1

520

610

300

600

690

300

 

 

 

4

1120

1400

700

870

1090

700

1120

1400

700

038

0.50

1/2

3

1000

1250

630

780

980

630

1000

1250

630

2

860

1080

540

670

840

540

860

1080

540

 

 

 

 

 

 

1

730

900

450

730

900

450

 

 

 

4

1460

1730

870

1140

1350

870

1560

1850

870

049

0.75

1

3

1300

1550

780

1020

1210

780

1400

1650

780

2

1120

1330

670

870

1040

670

1200

1430

670

 

 

 

 

 

 

1

940

1120

560

1010

1200

560

 

 

 

4

1670

2050

1020

1300

1600

1020

1860

2280

1020

064

0.75

1

3

1500

1825

920

1160

1430

920

1650

2050

920

2

1280

1580

790

1000

1230

790

1430

1750

790

 

 

 

 

 

 

1

1080

1320

660

1200

1470

660

 

 

 

4

1620

2190

1050

1270

1650

1050

1690

2230

1050

072

0.75

1

3

1500

1950

980

1170

1520

980

1600

2100

980

2

1400

1830

910

1100

1420

910

1400

1850

910

 

 

 

 

 

 

1

1320

1700

850

1240

1620

850

WSHP OPEN CONTROLS — The ECM fan is controlled by an interface board that converts the fan speed outputs from the WSHP Open control board to the signal used by the ECM mo- tor (see Fig 35). The indicator LEDs allow the service techni- cian to view the airflow mode that the WSHP Open control is commanding. The table below indicates the illuminated LEDs for each fan mode.

ECM INDICATORS LEDs

SPEED

G

Fan Only

G + Y1

Low Fan

G + Y1 + Y2

Med Fan

G + Y1 +W

High Fan

NOTE: Power must be off to the unit for at least three seconds before the ECM will recognize a speed change. The motor will recognize a change in the CFM Adjust setting (SW7 and SW8) while the unit is powered.

The WSHP Open controller provides four different airflow settings which can be set between the lowest airflow (tap 1) to the highest airflow (tap 4). The lowest three airflow settings (Fan Only, Low, and Medium) are set using SW3 and SW 4 while the highest airflow (High) is set independently using SW5 and SW6. This provides the ability to better adjust the fan performance of the unit to meet the required load conditions.

Cooling and Heating — The SW3 and SW4 DIP switch set- tings determine the fan airflow (cfm) to be used during normal Fan Only, Cooling, Heating, and Dehumidification modes (see

Table 14A). The fan speed and airflow is independent from the compressor capacity control. During Fan Only operation, the fan will operate at the Fan Only airflow value specified in the table for the appropriate tap setting. Once either cooling or heating is required and the compressor is energized, the fan will increase the minimum airflow across the coil to the value defined by the low fan selection. Coil freeze protection and ex- cessive discharge air temperature protection are integral parts of the WSHP Open controller function so the fan airflow can increase to medium or high airflow as required and indepen- dent of compressor capacity to prevent excessively hot or cold supply air temperature and coil freeze-up. The selection of the high fan airflow setting is independent of the other fan airflow settings and is defined in Table 14B. The high airflow must be chosen so that it is equal to or greater than the medium fan air- flow. Therefore the tap setting for high fan (SW5 and SW6) MUST equal or exceed the tap chosen for the SW3 and SW4.

Dehumidification — When Dehumidification is used, the fan operates at the airflow setting defined by the Medium Fan air- flow setting and the tap position of SW3 and SW4.

CFM Adjust — The CFM Adjust setting allows the balancer to fine tune the actual airflow. SW7 and SW8 are used to set the CFM Adjustment if necessary. The NORM setting is the factory default. The (+) or (-) settings provide the ability to ad- just the airflow by either +15% or -15% as needed. A test posi- tion is also provided but should not be used (see Table 11).

28

Page 28
Image 28
Carrier PTV, 50PTH specifications Blower Performance Data