20 LEGEND

20a50-8363Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background LEGEND

a50-8363

Complete C

AL

Alarm Relay Contacts

ASTAT

Aquastat

BM

Blower Motor

BMC

Blower Motor Capacitor

BR

Blower Relay

CB

Circuit Breaker

CCCompressor Contactor

CO

Sensor, Condensate Overflow

DTS

Discharge Temperature Switch

ECM

Electronically Commutated Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

HP

High-Pressure Switch

HPWS

High-Pressure Water Switch

HWG

Hot Water Generator

JW1

Clippable Field Selection Jumper

LOC

Loss of Charge Pressure Switch

LON

Local Operating Network

MV

Motorized Valve

MVES

Motorized Valve End Switch

NEC

National Electrical Code

P1

Field Wiring Terminal Block

RVS

Reversing Valve Solenoid

TRANS

Transformer

*Optional Wiring.

Field Line Voltage Wiring

Field Low Voltage Wiring

Printed Circuit Trace

Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Temperature Switch

Thermistor

Ground

Wire Nut

Relay Contacts - N.C.

Relay Contacts - N.O.

Low Pressure Switch

High Pressure Switch

Splice Cap

Circuit Breaker

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer is wired to 460 v (BLK/RED) lead for 460/3/60 units. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Typical thermostat wiring shown. Refer to thermostat installation instructions for wiring to the unit. Ther- mostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.Factory cut JW1 jumper. Dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)

8.Aquastat is supplied with unit and must be wired in series with the hot leg to the pump. Aquastat is rated for voltages up to 277-v.

9.Optional LON wires. Only connect if LON connection is desired at the wall sensor.

10.Fan motors are factory wired for medium speed. For high or low speed, remove BLU wire from fan motor speed tap “M” and connect to “H” for high speed or “L” for low speed.

11.For low speed, remove BLK wire from BR “6” and replace with RED. Connect BLK and BRN wires together.

12.For blower motors with leads. For medium or low speed, disconnect BLK wire from BR “6”. Connect BLK and ORG/PUR wire together. Connect RED for low or BLU for medium to BR “6”.

13.The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR, and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.

Fig. 21 — Wiring of 50PTH,PTV,PTD026-072 Units with Complete C and LON Controller, Three Phase (460 V)