Carrier specifications 50PTH,PTV,PTD Electrical Data

Models: 50PTH PTV

1 64
Download 64 pages 3.31 Kb
Page 13
Image 13
Table 4 — 50PTH,PTV,PTD Electrical Data

conform to the Class II temperature limitations described in the NEC.

Refer to unit wiring diagrams Fig. 15-24 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. For Deluxe D with WSHP Open controls 3-phase units and Complete C with Open controls single-phase and 3-phase units contact Application Engineering. Refer to Table 4 for fuse sizes.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.

Operating voltage must be the same voltage and phase as shown in electrical data shown in Table 4.

Make all final electrical connections with a length of flexi- ble conduit to minimize vibration and sound transmission to the building.

POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the line side of the compressor contactor terminal as shown in Fig. 25. See Table 4 for amperage ratings to provide correct wire and maximum overcurrent protection sizing.

SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter- mine the percentage voltage imbalance:

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

 

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 volts

BC = 464 volts

AC = 455 volts

Average Voltage = 452 + 464 + 455 3

=1371

3

= 457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v. Determine percent voltage imbalance.

% Voltage Imbalance =

100 x

7

457

=

1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.

NOTE: If more than 2% voltage imbalance is present, contact your local electric utility.

208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.

460-VOLT OPERATION — Units using 460-v and an ECM (electronically commutated motor) fan motor, modulating HWR, and/or internal secondary pump will require a neutral wire from the supply side in order to feed accessory with 265-v.

Table 4 — 50PTH,PTV,PTD Electrical Data

50PTH,

 

VOLTAGE

COMPRESSOR

FAN

TOTAL

MIN

MAX

 

UNITS WITH HWR

 

PTV, PTD

V-PH-Hz*

 

 

MOTOR

CIRCUIT

FUSE/

REHEAT

TOTAL

MIN

MAX

MIN/MAX

RLA

LRA

UNIT FLA

PUMP

UNIT

CIRCUIT

FUSE/

UNITS

 

 

 

 

FLA

 

AMPS

HACR

FLA

FLA

AMP

HACR

 

 

 

 

 

 

 

 

 

026

208/230-1-60

197/254

10.3

52.0

4.3

14.6

17.2

25

0.8

15.4

18.0

25

 

208/230-1-60

197/254

16.7

82.0

4.3

21.0

25.2

40

0.8

21.8

26.0

40

038

208/230-3-60

197/254

11.2

58.0

4.3

15.5

18.3

25

0.8

16.3

19.1

30

 

460-3-60

414/506

4.5

29.0

4.1

8.6

9.7

15

0.7

9.3

10.4

15

 

208/230-1-60

197/254

21.2

96.0

7.0

28.2

33.5

50

1.07

29.3

34.6

50

049

208/230-3-60

197/254

13.5

88.0

7.0

20.5

23.9

35

1.07

21.6

24.9

35

 

460-3-60

414/506

6.4

41.0

6.9

13.3

14.9

20

1.07

14.4

16.0

20

 

208/230-1-60

197/254

25.6

118.0

7.0

32.6

39.0

60

1.07

33.7

40.1

60

064

208/230-3-60

197/254

17.6

123.0

7.0

24.6

29.0

45

1.07

25.7

30.1

45

 

460-3-60

414/506

9.0

62.0

6.9

15.9

18.2

25

1.07

17.7

19.2

25

072

208/230-1-60

197/254

27.2

150.0

7.0

34.2

41.0

60

1.07

35.3

42.1

60

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

LRA

Locked Rotor Amps

RLA

Rated Load Amps

HWR

Hot Water Reheat

*The 460-v units using an ECM (electronically commutated motor) fan motor, modulating HWR, and/or an internal secondary pump will require a neutral wire from the supply side in order to feed the accessory with 265-v.

13

Page 13
Image 13
Carrier specifications 50PTH,PTV,PTD Electrical Data