Carrier 50PTH, PTV specifications Pre-Start-Up, B — WSHP Open — High Fan Airflow

Models: 50PTH PTV

1 64
Download 64 pages 3.31 Kb
Page 29
Image 29
Table 14B — WSHP Open — High Fan Airflow

Table 14A — WSHP Open — Fan Only / Low Fan and Med Fan Airflow

50PT UNIT

MAX

FAN MOTOR

TAP SETTING

SW 3

SW 4

FAN ONLY

COOLING AND

COOLING AND

SIZE

ESP

HP

(SW 1)

(SW 2)

HEATING LOW FAN

HEATING MED FAN

 

 

 

 

 

4

OFF

OFF

475

920

1050

 

 

 

 

 

 

 

 

 

26

0.5

0.5

3

OFF

ON

425

825

950

 

 

 

 

 

 

2

ON

OFF

370

710

820

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

300

600

690

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

700

1120

1400

 

 

 

 

 

 

 

 

 

38

0.5

0.5

3

OFF

ON

630

1000

1250

 

 

 

 

 

 

2

ON

OFF

540

860

1080

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

450

730

900

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

870

1560

1850

 

 

 

 

 

 

 

 

 

49

0.75

1

3

OFF

ON

780

1400

1650

 

 

 

 

 

 

2

ON

OFF

670

1200

1430

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

560

1010

1200

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

1020

1860

2280

 

 

 

 

 

 

 

 

 

64

0.75

1

3

OFF

ON

920

1650

2040

 

 

 

 

 

 

2

ON

OFF

780

1430

1750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

660

1200

1470

 

 

 

 

 

 

 

 

 

 

 

 

4

OFF

OFF

1050

1600

2230

 

 

 

 

 

 

 

 

 

72

0.75

1

3

OFF

ON

980

1600

2100

 

 

 

 

 

 

2

ON

OFF

910

1400

1850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

ON

ON

850

1240

1620

 

 

 

 

 

 

 

 

 

NOTE: Factory default setting shown bold.

IMPORTANT: The tap setting for high fan MUST equal or exceed the tap setting for fan only/low/med fan

Table 14B — WSHP Open — High Fan Airflow

50PT UNIT SIZE

MAX ESP

FAN MOTOR HP TAP SETTING

SW 5

SW 6

COOLING AND HEATING HIGH FAN

 

 

4

OFF

OFF

1060

 

 

 

 

 

 

 

26

 

3

OFF

ON

950

0.5

0.5

 

 

 

 

 

ON

OFF

820

 

 

 

2

 

 

1

ON

ON

690

 

 

 

4

OFF

OFF

1400

38

 

3

OFF

ON

1350

0.5

0.5

 

 

 

 

 

ON

OFF

1350

 

 

 

2

 

 

1

ON

ON

1350

 

 

 

4

OFF

OFF

1850

49

 

3

OFF

ON

1660

0.75

1

 

 

 

 

 

ON

OFF

1430

 

 

 

2

 

 

1

ON

ON

1350

 

 

 

4

OFF

OFF

2280

64

 

3

OFF

ON

2050

0.75

1

 

 

 

 

 

ON

OFF

1750

 

 

 

2

 

 

1

ON

ON

1470

 

 

 

4

OFF

OFF

2230

72

 

3

OFF

ON

2100

0.75

1

 

 

 

 

 

ON

OFF

1870

 

 

 

2

 

 

1

ON

ON

1670

NOTE: Factory default setting shown bold.

IMPORTANT: The tap setting for high fan MUST equal or exceed the tap setting for fan only/low/med fan

PRE-START-UP

System Checkout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure:

1.Voltage is within the utilization range specifications of the unit compressor and fan motor and voltage is balanced for 3-phase units.

2.Fuses, breakers and wire are correct size.

3.Low voltage wiring is complete.

4.Piping and system flushing is complete.

5.Air is purged from closed loop system.

6.System is balanced as required. Monitor if necessary.

7.Isolation valves are open.

8.Water control valves or loop pumps are wired.

9.Condensate line is open and correctly pitched.

10.Transformer switched to lower voltage tap if necessary.

11.Blower rotates freely — shipping support is removed.

12.Blower speed is on correct setting.

13.Air filter is clean and in position.

14.Service/access panels are in place.

15.Return-air temperature is between 40 to 80 F heating and 50 to 110 F cooling.