Carrier PTV, 50PTH specifications Field-SuppliedSensors for, WSHP Open Controller, SPT Sensors

Models: 50PTH PTV

1 64
Download 64 pages 3.31 Kb
Page 24
Image 24
Table 5 — Field-Supplied Sensors for

CAPACITOR

COMPLETE C CONTROL

COMPRESSOR CONTACTOR

 

LINE

WSHP Open Controller LOAD

TRANSFORMER

ECM CONTROL

BOARD

 

Fig. 25 — 50PTH,PTV,PTD Typical Single-Phase Line Voltage Power Connection

WSHP OPEN WIRING — The WSHP Open controller will be factory mounted to the unit control panel and wired to the Complete C or Deluxe D control board, however, the system wiring will need to be completed utilizing WSHP Open con- troller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation includes harness, LWT (leaving water temperature), supply air, and condensate sensor.

Table 6 — SPT Sensors WARNING

Disconnect all power to the unit before performing mainte- nance or service. Unit may automatically start if power is not disconnected. Failure to follow this warning could cause personal injury, death, and/or equipment damage.

Wiring Sensors to Inputs — Sensors can be wired to the WSHP Open controller’s inputs. See Table 5.

All field control wiring that connects to the WSHP Open con- troller must be routed through the raceway built into the corner post. The raceway provides the UL required clearance between high and low-voltage wiring.

1.Pass control wires through the hole provided in the corner post.

2.Feed the wires through the raceway to the WSHP Open controller.

3.Connect the wires to the removable Phoenix connectors.

4.Reconnect the connectors to the board.

Field-Supplied Sensor Hardware — The WSHP Open con- troller is configurable with the following field-supplied sen- sors. See Table 5.

Table 5 — Field-Supplied Sensors for

WSHP Open Controller

SENSOR

NOTES

Space Temperature Sensor

Field Installed (Must be used with

(SPT)

WSHP Open controller.)

Outdoor Air

Network Sensor

Temperature Sensor

 

Indoor Air Quality Sensor

Required only for demand

(Separate Sensor)

control ventilation.

Space Relative

Separate Sensor

Humidity Sensor

 

NOTE: BACview6 Handheld or Virtual BACview can be used as the user interface.

For specific details about sensors, refer to the literature sup- plied with the sensor.

Wiring a SPT Sensor — A WSHP Open controller is connect- ed to a wall-mounted space temperature (SPT) sensor to moni- tor room temperature using a Molex plug.

The WSHP Open system offers the following SPT sensors. See Table 6.

 

Table 6 — SPT Sensors

 

 

 

 

SENSOR

PART

 

FEATURES

NUMBER

 

 

 

 

SPT

SPS

• Local access port

Standard

• No operator control

 

 

 

• Slide potentiometer to adjust set point

SPT Plus

SPPL

• Manual on button to override schedule

• LED to show occupied status

 

 

 

 

• Local access port

 

 

LCD display

 

 

Manual on button to override schedule

SPT Pro

 

Warmer and cooler buttons to adjust set point

SPP

Info button to cycle through zone and outside

 

 

 

air temperatures, set points, and local override

 

 

 

time

 

 

Local access port

 

 

• LCD display

 

 

• Manual on button to override schedule

SPT Pro

 

• Warmer and cooler buttons to adjust set point

SPPF

• Info button to cycle through zone and outside

Plus

 

air temperatures, set points, and local override

 

 

 

 

 

time

 

 

• Local access port

 

 

• Fan speed*

*The SPT Pro Plus fan speed adjustment has no effect in this application.

Wire SPT sensors to the WSHP Open controller’s Rnet port. An Rnetbus can consist of any of the following combina- tions of devices wired in a daisy-chain configuration:

1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

1 to 4 SPT Standard sensors

1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor

Any of the above combinations, plus up to 2 BACview6 Handheld but no more than 6 total devices

NOTE: If the Rnetbus has multiple SPT Standard sensors, each sensor must be given a unique address on the Rnetbus. See the Carrier Open Sensor Installation Guide.

Use the specified type of wire and cable for maximum signal integrity. See Table 7.

Table 7 — Rnet Wiring Specifications

RNET WIRING SPECIFICATIONS

 

Description

 

4 conductor, unshielded, CMP,

 

 

plenum rated cable

 

 

 

 

Conductor

 

18 AWG

 

Maximum Length

 

500 ft

 

Recommended Coloring

 

Jacket: white

 

 

Wiring: black, white, green, red

 

 

 

 

UL Temperature

 

32 to 167 F

 

Voltage

 

300-vac, power limited

 

Listing

 

UL: NEC CL2P, or better

 

LEGEND

 

AWG — American Wire Gage

 

CMP

Communications Plenum Cable

 

NEC

National Electrical Code

 

UL

Underwriters Laboratories

 

24

Page 24
Image 24
Carrier PTV, 50PTH specifications Field-SuppliedSensors for, WSHP Open Controller, SPT Sensors, Rnet Wiring Specifications