vide cooling to the space when required. Should the capacity be insufficient for a period greater than 5 minutes, or should a high humidity condition occur, then the compressor will be started to satisfy the load. Should the SAT reach the minimum cooling SAT limit, the economizer valve will close during compressor operation.

Heating — Additionally, the economizer control will open the water valve should the entering water loop temperature be suit- able for heating (at least 5° F above space temperature) and heat is required. The valve will be controlled in a similar man- ner except to satisfy the heating requirement. Should the coil capacity be insufficient to satisfy the space load for more than 5 minutes, then the compressor will be started to satisfy the load. Should the SAT reach the maximum heating SAT limit, the economizer valve will close during compressor operation.

DEMAND LIMIT — The WSHP Open controller has the ability to accept three levels of demand limit from the network. In response to a demand limit, the unit will decrease its heating set point and increase its cooling set point to widen the range in order to immediately lower the electrical demand. The amount of temperature adjustment in response is user adjustable for both heating and cooling and for each demand level. The re- sponse to a particular demand level may also be set to zero.

CONDENSER WATER LINKAGE — The control pro- vides optimized water loop operation using an universal con- troller (UC) open loop controller. Loop pump operation is auto- matically controlled by WSHP equipment occupancy sched- ules, unoccupied demand and tenant override conditions. Positive pump status feedback prevents nuisance fault trips. The condenser water linkage operates when a request for con- denser water pump operation is sent from each WSHP to the loop controller. This request is generated whenever any WSHP is scheduled to be occupied, is starting during optimal start (for warm-up or pull down prior to occupancy), there is an unoccu- pied heating or cooling demand, or a tenant pushbutton over- ride. At each WSHP, the water loop temperature and the loop pump status is given. The WSHP will NOT start a compressor until the loop pumps are running or will shutdown the com- pressors should the pumps stop. This prevents the WSHP from operating without water flow and thus tripping out on refriger- ant pressure, causing a lockout condition. The WSHP Open controller control will prevent this from occurring. Also, the loop controller can be configured to start the pumps only after a configurable number of WSHPs are requesting operation (from 1-"N"). This can be used to prevent starting the entire loop op- eration for only one WSHP. Meanwhile, the WSHPs will not operate if the loop pump status is off and therefore the WSHP compressor will not run.

COMPLETE C AND DELUXE D BOARD

SYSTEM TEST

Test mode provides the ability to check the control opera- tion in a timely manner. The control enters a 20-minute test mode by momentarily shorting the test terminals. All time de- lays are sped up 15 times. The following operations are com- mon to both Complete C and Deluxe D controls.

Test Mode — To enter Test mode, cycle the fan 3 times within 60 seconds. The LED will flash a code representing the last fault when entering the Test mode. The alarm relay will also power on and off during Test mode. See Tables 27 and 28. To exit Test mode, short the terminals for 3 seconds or cycle the fan 3 times within 60 seconds.

NOTE: The flashing code and alarm relay cycling code will both have the same numerical label. For example, flashing code 1 will have an alarm relay cycling code 1. Code 1 indi- cates the control has not faulted since the last power off to power on sequence.

Table 27 — Complete C Control Current LED

Status and Alarm Relay Operations

LED STATUS

DESCRIPTION OF OPERATION

ALARM RELAY

 

 

Normal Mode

Open

 

On

Normal Mode with

Cycle

 

(closed 5 sec.,

 

 

PM Warning

 

 

open 25 sec.)

 

 

 

 

Off

Complete C Control is

Open

 

non-functional

 

 

 

Slow Flash

Fault Retry

Open

Fast Flash

Lockout

Closed

Slow Flash

 

Open,

Over/Under Voltage Shutdown

(Closed after

 

 

 

15 minutes)

Flashing Code 1

Test Mode — No fault in memory

Cycling Code 1

Flashing Code 2

Test Mode —

Cycling Code 2

HP Fault in memory

 

 

 

Flashing Code 3

Test Mode —

Cycling Code 3

LP Fault in memory

 

 

 

Flashing Code 4

Test Mode —

Cycling Code 4

FP1 Fault in memory

 

 

 

Flashing Code 5

Test Mode —

Cycling Code 5

FP2 Fault in memory

 

 

 

Flashing Code 6

Test Mode —

Cycling Code 6

CO Fault in memory

 

 

 

Flashing Code 7

Test Mode — Over/Under

Cycling Code 7

shutdown in memory

 

 

 

Flashing Code 8

Test Mode — PM in memory

Cycling Code 8

Flashing Code 9

Test Mode — FP1/FP2

Cycling Code 9

Swapped Fault in memory

 

 

 

 

LEGEND

 

CO

Condensate Overflow

 

FP

Freeze Protection

 

HP

High Pressure

 

LED

Light-Emitting Diode

 

LP

Low Pressure

 

PM

Performance Monitor

 

NOTES:

1.Slow flash is 1 flash every 2 seconds.

2.Fast flash is 2 flashes every 1 second.

3.EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by a 10-second pause. This sequence will repeat continually until the fault is cleared.

Table 28 — Complete C Control LED Code and

Fault Descriptions

LED

FAULT

DESCRIPTION

CODE

 

 

 

1

No fault in memory

There has been no fault since

 

 

 

the last power-down to power-

 

 

 

up sequence

 

2

High-Pressure Switch

HP switch opens instantly

 

3

Low-Pressure Switch

LP switch opens for

 

 

 

30 continuous seconds before

 

 

 

or during a call (bypassed for

 

 

 

first 60 seconds)

 

4

Freeze Protection Coax

FP1 below Temp limit for

 

 

— FP1

30 continuous seconds

 

 

 

(bypassed for first 60 seconds of

 

 

 

operation)

 

5

Freeze Protection Air Coil —

FP2 below Temp limit for

 

 

FP2

30 continuous seconds

 

 

 

(bypassed for first 60 seconds of

 

 

 

operation)

 

6

Condensate overflow

Sense overflow (grounded) for

 

 

 

30 continuous seconds

 

7

Over/Under Voltage

"R" power supply is <19VAC or

(Autoreset)

Shutdown

>30VAC

 

8

PM Warning

Performance Monitor Warning

 

 

 

has occurred.

 

9

FP1 and FP2

FP1 temperature is higher than

 

 

Thermistors are swapped

FP2 in heating/test mode, or

 

 

 

FP2 temperature is higher than

 

 

 

FP1 in cooling/test mode.

 

LEGEND

 

FP

Freeze Protection

 

HP

High Pressure

 

LED

Light-Emitting Diode

 

LP

Low Pressure

 

PM

Performance Monitor

 

42

Page 42
Image 42
Carrier PTV, 50PTH Complete C and Deluxe D Board System Test, Complete C Control LED Code Fault Descriptions, Led