Carrier PTV Heating Cycle Analysis, Cooling Cycle Analysis, Flow Rate Gpm, Temp. Diff. Deg. F

Models: 50PTH PTV

1 64
Download 64 pages 3.31 Kb
Page 64
Image 64
HEATING CYCLE ANALYSIS

HEATING CYCLE ANALYSIS

PSI

SAT

- - - - - - - - - - - - - -

°F

AIR

COIL

°F

EXPANSION

VALVE

COAX

°F

SUCTION

COMPRESSOR

DISCHARGE

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - -

 

°

F

 

 

 

 

 

 

 

a50-8449

 

 

 

 

 

 

 

 

 

LIQUID LINE

 

°F

 

 

°F

 

 

 

 

 

PSI

 

 

 

PSI

 

 

 

 

 

 

 

 

 

FLUID IN

 

FLUID OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOOK UP PRESSURE DROP IN TABLES 20-23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO DETERMINE FLOW RATE

COOLING CYCLE ANALYSIS

PSISAT

- - - - - - - - - - - - - - - - - - - - - - - - - - ALONG DOTTED LINE

°F

AIR

COIL

°F

EXPANSION

VALVE

COAX

°F

SUCTION

COMPRESSOR

DISCHARGE

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - LINECUT

 

 

 

 

 

°

F

 

 

 

 

 

 

 

 

 

a50-8450

 

 

 

LIQUID LINE

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

PSI

 

 

 

PSI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLUID IN

 

FLUID OUT

LOOK UP PRESSURE DROP IN TABLES 20-23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO DETERMINE FLOW RATE

HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =

 

FLOW RATE (GPM) x

TEMP. DIFF. (DEG. F) x

 

FLUID FACTOR* =

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Btu/hr)

SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE

=

 

(DEG F)

 

 

 

 

 

 

 

 

 

 

 

SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE

=(DEG F)

*Use 500 for water, 485 for antifreeze.

Copyright 2010 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53500079-01

Printed in U.S.A.

Form 50PT-4SI

Pg CL-2

7-10

Replaces: 50PT-3SI