Carrier PTV, 50PTH specifications CC— Compressor Contactor

Models: 50PTH PTV

1 64
Download 64 pages 3.31 Kb
Page 16
Image 16
Manual background

BM (ECM)

SW1

 

SW2

 

SW3

 

SW4

 

SW5

 

SW6

 

SW7

 

SW8

 

SW9

 

OFF

ON

 

ECM

 

INTERFACE

16

BOARD

 

 

LEGEND

AL

Alarm Relay Contacts

ASTAT

Aquastat

BM

Blower Motor

BR

Blower Relay

CB

Circuit Breaker

CCCompressor Contactor

CO

Sensor, Condensate Overflow

DTS

Discharge Temp Switch

ECM

Electronically Commutated Motor

FP1

Sensor, Water Coil Freeze Protection

FP2

Sensor, Air Coil Freeze Protection

HP

High-Pressure Switch

HWG

Hot Water Generator

JW1

Jumper, Alarm

LOC

Loss of Charge Pressure Switch

MV

Motorized Valve

NEC

National Electrical Code

P1

Field Wiring Terminal Block

RVS

Reversing Valve Solenoid

TRANS

Transformer

Field Line Voltage Wiring

Field Low Voltage Wiring

Printed Circuit Trace

Optional Wiring

Relay/Contactor Coil

Condensate Pan

Solenoid Coil

Temperature Switch

Thermistor

Ground

Wire Nut

 

 

BM (ECM)

 

 

J1

 

 

Y

W

R

S1

 

CFM

 

 

SW1

O

 

 

 

 

 

SW2

 

G

 

 

 

 

SW3

 

 

 

 

 

 

 

SW4

 

 

 

 

 

 

 

SW5

 

Y2

G

 

 

 

 

SW6

 

 

 

 

 

SW7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW8

 

Y1

G

 

 

 

 

SW9

 

 

 

 

 

 

OFF

ON

 

 

 

 

 

 

 

G

G

 

 

 

 

G

DEHUM

 

 

TB1

 

 

 

 

 

 

R

C

Y2 Y1 G

O

W

C

R DH AL1 A

A

AL1

ECM INTERFACE BOARD LAYOUT

NOTES:

1.Compressor and blower motor thermally protected internally.

2.All wiring to the unit must comply with NEC and local codes.

3.Transformer for 208/230 v will be connected for 208 v operation. For 230 v operation, disconnect RED lead at L1 and attach ORN lead to L1. Insulate open end of RED lead. Transformer for 220/ 240 v will be connected for 220 v operation. For 240 v operation, disconnect RED lead at L1 and attach ORN lead to L1. Transformer is energy limiting or may have circuit breaker.

4.FP1 thermistor provides freeze protection for water. When using antifreeze solutions, cut JW3 jumper.

5.Typical Aquazone™ thermostat wiring shown. Refer to thermostat installation instructions for wir- ing to the unit. Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage.

6.24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry contact will be available between AL1 and AL2.

7.Transformer secondary ground via Complete C board standoffs and screws to control box. (Ground available from top two standoffs as shown.)

8.Aquastat is field-supplied and must be wired in series with the hot leg to the pump. Aquastat is rated for voltage up to 277 v.

9.Place jumpers on 2 and 3, ECM board, when dehumidification mode is used.

Fig. 17 — Wiring of 50PTH,PTV,PTD026-072 Units with Complete C Controller, Three Phase (208/230 V)

Page 16
Image 16
Carrier PTV, 50PTH specifications CC— Compressor Contactor