Table 32 — WSHP Troubleshooting (cont)
FAULT | HEATING | COOLING | POSSIBLE CAUSE | SOLUTION | |
High Head Pressure | X |
| Reduced or no airflow in heating | Check for dirty air filter and clean or replace. | |
|
|
|
| Check fan motor operation and airflow restrictions. | |
|
|
|
| External static too high. Check blower performance per Tables | |
|
| X | Reduced or no water flow in | Check pump operation or valve operation/setting. | |
|
|
| cooling | Check water flow adjust to proper flow rate. See Tables 19 and 24. | |
|
|
|
| ||
|
| X | Inlet water too hot | Check load, loop sizing, loop backfill, ground moisture. | |
| X |
| Air temperature out of range in | Bring | |
|
|
| heating |
| |
|
| X | Scaling in water heat exchanger | Perform condenser cleaning. | |
| X | X | Unit overcharged | Check superheat and subcooling. Reweigh in charge. | |
| X | X | Noncondensables in system | Remove refrigerant, evacuate system and charge unit. | |
| X | X | Restricted metering device | Check superheat and subcooling per Tables | |
Low Suction Pressure | X |
| Reduced water flow in heating | Check pump operation or water valve operation/setting. | |
|
|
|
| Plugged strainer or filter. Clean or replace. | |
|
|
|
| Check water flow adjust to proper flow rate. | |
| X |
| Water temperature out of range | Bring water temperature within design parameters. | |
|
| X | Reduced airflow in cooling | Check for dirty air filter and clean or replace. | |
|
|
|
| Check fan motor operation and airflow restrictions. | |
|
|
|
| External static too high. Check blower performance per Tables | |
|
| X | Air temperature out of range | Too much cold vent air. Bring entering air temperature within design | |
|
|
|
| parameters. | |
| X | X | Insufficient charge | Check for refrigerant leaks. | |
Low Discharge Air | X |
| Too high airflow | Check blower performance per Tables | |
Temperature in Heating | X |
| Poor performance | See “Insufficient Capacity.” | |
High Humidity |
| X | Too high airflow | Check blower performance per Tables | |
|
| X | Unit oversized | Recheck loads and sizing check sensible cooling load and heat pump | |
|
|
|
| capacity. | |
Low Refrigerant Suction | X |
| Normal operation | Check/compare with unit Installation Manual for typical operating temper- | |
Pressure |
|
|
| atures and pressures chart. | |
| X |
| Reduced water flow | Check pump operation. | |
|
|
|
| Check strainer or filter. | |
|
|
|
| Improper flow regulator. | |
| X |
| Water temperature out of range | Bring water temperature within proper range. | |
| X |
| Scaling in water to refrigerant | Conduct water quality analysis. | |
|
|
| heat exchanger |
| |
|
| X | Reduced airflow | Check for dirty air filter. | |
|
|
|
| Check for dirty air coil. | |
|
|
|
| Check fan motor operation. | |
|
|
|
| External static pressure exceeds fan operating parameters. | |
| X | X | Return air temperature below | Space temperature too cold. | |
|
|
| minimum |
| |
|
|
|
| Excessive fresh air. | |
|
| X | Supply air bypassing to return air | Check for leaking ductwork. | |
|
|
| stream (zone systems). |
| |
| X | X | Insufficient refrigerant charge | Locate and repair leak. | |
| X | X | Improperly located TXV sensing | Locate bulb on suction line between reversing valve and compressor. | |
|
|
| bulb |
| |
| X | X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. | |
|
|
| device | Plugged TXV strainer. | |
|
|
|
| ||
High Refrigerant Superheat | X | X | Insufficient refrigerant charge | Locate and repair leak. | |
| X | X | Improperly located TXV sensing | Locate bulb on suction line between reversing valve and compressor. | |
|
|
| bulb |
| |
| X | X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. | |
|
|
| device | Plugged TXV strainer. | |
|
|
|
| ||
High Refrigerant | X | X | Excessive refrigerant charge | Remove refrigerant as needed. | |
Subcooling |
|
|
|
| |
X | X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. | ||
| |||||
|
|
| device | Plugged TXV strainer. | |
|
|
|
| ||
TXV and/or Low Pressure | X |
| Normal operation | May occur when entering water temperature is close to minimum. | |
Tubing Frosting |
|
|
|
| |
X | X | Insufficient refrigerant charge | Locate and repair leak. | ||
| |||||
| X | X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. | |
|
|
| device | Plugged TXV strainer. | |
|
|
|
| ||
Equalizer Line Condensing | X | X | Failed or restricted metering | Failed TXV power head, capillary or sensing bulb. | |
or Frosting |
|
| device | Plugged TXV strainer. | |
|
|
|
|
LEGEND
LED —
RV — Reversing Valve
TXV — Thermostatic Expansion Valve
53