APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
SCREEN NAME | POINT NAME | PASSWORD | EDITABLE | RANGE | DEFAULT | NOTES | ||
|
|
| LEVEL |
|
|
|
| |
|
|
|
|
| Off, Fan Only,Economize, |
|
| |
|
| Operating Mode |
|
| Cooling, Heating, Cont Fan, Test, |
| Displays unit operating mode | |
|
|
|
|
| Start Delay, Dehumidify |
|
| |
|
| Fan Operating Mode |
|
| Auto/Continuous/Always On |
| Displays how the fan is configured | |
|
|
|
|
| to operate | |||
|
|
|
|
|
|
| ||
|
| Occupancy Status |
|
| Unoccupied/Occupied |
| Displays the current occupancy status | |
|
|
|
|
| Always Occupied/Local Schedule/ |
|
| |
|
|
|
|
| BACnet Schedule/BAS Keypad/ |
| Displays the origin of the | |
|
| Occupancy Control |
|
| Occupied Contact/Holiday Schedule/ |
| ||
|
|
|
|
| occupancy control | |||
|
|
|
|
| Override Schedule/Pushbutton |
| ||
|
|
|
|
|
|
| ||
|
|
|
|
| Override/Unoccupied None |
|
| |
|
| Outside Air |
|
| ° F |
| Displays OAT (Viewable only if OAT | |
|
| Temperature |
|
|
| is a network broadcast) | ||
|
|
|
|
|
| |||
|
| SPT |
|
| ° F |
| Displays SPT | |
|
| SPT Status |
|
| Normal/Above Limit/Below |
| Displays the SPT status | |
|
|
|
| Limit/Sensor Failure |
| |||
|
|
|
|
|
|
| ||
|
| SPT Sensor Status |
|
| Inactive/Connected |
| Displays the connection status | |
|
|
|
|
| of the Rnet sensor | |||
|
|
|
|
|
|
| ||
|
| Condensate Overflow |
|
| Normal/Alarm |
| Displays the status of the | |
|
|
|
|
| condensate overflow | |||
|
|
|
|
|
|
| ||
|
| Cooling Set Point |
|
| ° F |
| Displays the actual set point | |
|
|
|
|
| being used for cooling control | |||
|
|
|
|
|
|
| ||
|
| Heating Set Point |
|
| ° F |
| Displays the actual set point | |
| Unit | No Password |
|
| being used for heating control | |||
|
|
|
|
| ||||
Maintenance |
| required |
| ° F |
| Displays the offset values from the Rnet | ||
|
| Set Point Adjustment |
|
|
| user set point adjustment that is being | ||
|
|
|
|
|
|
| applied to the configured set points | |
|
| Auxiliary Heat Control |
|
| ° F |
| Displays the calculated set point being | |
|
| Set Point |
|
|
| used for auxiliary heating control | ||
|
|
|
|
|
| |||
|
| H2O Economizer |
|
| ° F |
| Displays the calculated set point being | |
|
| Control Set Point |
|
|
|
| used for economizer control | |
|
| Calculated IAQ/ |
|
|
|
| Displays the ventilation damper | |
|
| Ventilation Damper |
|
| % |
| ||
|
|
|
|
| position calculated by the DCV control | |||
|
| position |
|
|
|
| ||
|
|
|
|
|
|
| ||
|
| Active Compressor |
|
| 0/1/2 |
| Displays the actual number of | |
|
| Stages |
|
|
| compressor stages operating | ||
|
|
|
|
|
| |||
|
| SAT |
|
| ° F |
| Displays SAT | |
|
| Reset Filter Alarm |
| X | No/Yes |
| Used to reset the filter alarm timer after | |
|
|
|
| the filter has been cleaned or replaced | ||||
|
|
|
|
|
|
| ||
|
| Overflow Contact |
|
| Closed/Open |
| Displays the state of the condensate | |
|
|
|
|
| overflow switch contact | |||
|
|
|
|
|
|
| ||
|
| Occupancy Contact |
|
| Closed/Open |
| Displays the state of the external/ | |
|
|
|
|
| remote occupancy input switch contact | |||
|
|
|
|
|
|
| ||
|
|
|
|
| Inactive/Occupied/ |
| Provides capability to force the | |
|
| BAS/Keypad Override |
| X | Inactive | equipment to operate in an | ||
|
|
| Unoccupied | |||||
|
|
|
|
|
| occupied or unoccupied mode | ||
|
|
|
|
|
|
| ||
|
| OAT Input |
|
| N/A / Network |
| Displays if an OAT value is being | |
|
|
|
|
| received from the Network | |||
|
|
|
|
|
|
| ||
|
| BACnet |
| X |
|
| See TPI | |
|
| Keypad Configuration |
| X |
|
| Mapping | |
System Settings | Password |
| X |
|
| Changes password | ||
Network |
| X |
|
| See TPI | |||
|
|
|
|
| ||||
|
| BACnet Time Master |
| X |
|
| See TPI | |
|
| Clock Set |
| X |
|
| Changes clock/time setting | |
|
| Override Schedules |
|
| Inactive/Active Occupied |
|
| |
|
| Pushbutton Override |
|
| Inactive/Active Occupied |
|
| |
Occupancy | Keypad Override | No Password |
| Inactive/Active Occupied/Active |
| Used to display the active and | ||
| Unoccupied |
| ||||||
Maintenance |
| required |
|
| inactive occupancy control inputs | |||
Schedules |
| Inactive/Active Occupied |
| |||||
|
|
|
|
|
| |||
|
| Occupancy Contact |
|
| Inactive/Active Occupied |
|
| |
|
| BAS on/off |
|
| Inactive/Active Occupied |
|
| |
|
| Local Occupancy |
| X | Disable/Enable | Enable |
| |
|
| Schedules |
|
| ||||
|
|
|
|
|
|
| ||
|
| Local Holiday | User/Admin | X | Disable/Enable | Disable | Used to define which occupancy inputs | |
Schedule | Schedules | |||||||
Password level |
|
|
| are used to determine | ||||
Configuration | Local Override |
|
|
| ||||
access | X | Disable/Enable | Disable | occupancy mode. | ||||
|
| Schedules | ||||||
|
|
|
|
|
|
| ||
|
| BACnet Occupancy |
| X | Disable/Enable | Disable |
| |
|
| Schedules |
|
| ||||
|
|
|
|
|
|
| ||
| LEGEND |
|
|
|
|
| ||
BAS — Building Automation System |
|
|
|
|
| |||
DCV | — Demand Controlled Ventilation |
|
|
|
| |||
IAQ | — Indoor Air Quality |
|
|
|
|
| ||
OAT | — Outdoor Air Temperature |
|
|
|
|
| ||
RH | — Relative Humidity |
|
|
|
|
| ||
SAT — Supply Air Temperature |
|
|
|
|
| |||
SPT | — Space Temperature |
|
|
|
|
| ||
TPI | — Third Party Integration |
|
|
|
|
|
55