A-14
Cisco ONS 15310-MA SDH Reference Manual, Release 9.1 and Release 9.2
78-19417-01
Appendix A Specifications
Purcell FLX25GT Cabinet Specifications
Minimum required rate @ maximum operating temperature for ONS 15310-MA SDH + cabinet: NA
Maximum allowable rate for ONS 15310-MA SDH: 1.02 m3/min, 36 CFM
Maximum allowable rate for ONS 15310-MA SDH + cabinet: NA
Volumetric flow rate for ONS 15310-MA: 0.93 to 1.02 m3/min
Volumetric flow rate for ONS 15310-MA SDH + cabinet: NA
Pressure drop through equipment for minimum required and maximum allowable flow rates for
15310-MA SDH: 0.44 inch
Pressure drop through equipment for minimum required and maximum allowable flow rates for
15310-MA SDH + cabinet: 1.36 wg
Heat dissipation for maximum load and minimum load on ONS 15310-MA SDH stand alone full
chassis: 234 W
Heat dissipation for maximum load and minimum load on cabinet AC power with fully populated
15310-MA: 390 W
Heat dissipation for maximum load and minimum load on ONS 15310-MA SDH stand alone empty
chassis+fan tray: 48.15 W
Heat dissipation for maximum load and minimum load on cabinet AC power with empty
15310-MA:181 W
Power drop (Power in minus Power out) cabinet ONS 15310-MA SDH: power abs 390 W
Power drop (Power in minus Power out) ONS 15310-MA SDH stand alone: power abs 234 W
Intake and exhaust temperature (Delta) on cabinet: 2,9
Intake and exhaust temperature (Delta) on ONS 15310-MA SDH: 7,9
EC Class of Equipment for Cooling configuration: Class 1 for ONS 15310-MA SDH + cabinet
EC Class of Equipment for Cooling configuration: Class 2 for ONS 15310-MA SDH stand alone
A.4.3 ONS 15310-MA SDH OSP Statements
The ONS 15310-MA SDH can be installed in OSP with a sealed/weatherproof and GR-487-CORE,
Issue 2 complaint OSP cabinet.
The ONS 15310-MA SDH OSP was tested and qualified for sealed/weather-protected locations
environmental requirements of GR-487-CORE, Issue 2.
The ONS 15310E-MA SDH OSP was tested and qualified to the non-weather protected locations
environmental requirements of EN300-019 1-4 and 2-4 Class T 4.2H and 4M5.
The ONS 15310E-MA SDH OSP was tested and qualified for the weather-protected locations
environmental requirements of EN 300-019-1-3 and EN 300-019-1-3 Class 3.3 and for WW EMC
requirements.
NEBS compliance covers FCC and other WW EMC requirements (based on CISPR22 and IEC
61000-4-2 to12 standards).