INSTALLATION
EATONPowerware®5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S164201730Rev 2
www.powerware.com
24
Installing the Rail Kit
CAUTION
TheUPS and EBM are heavy (see page 52). A minimum of two people are required to lift the
cabinetsinto the rack.
NOTE Mountingrails are required for each UPS and EBM cabinet. If mounting rails are not
alreadyinstalled in your rack, contact your local distributor to order rail kits.
To install the rail kit:
1. Adjust the rail size for the depth of your rack.
2. Select the proper holes in the rail for positioning the UPS in the
desired location in the rack.
3. Using two M5 washers and two M5 screws, attach the rail to the
rear of the rack (see Figure 4).
4. Secure the rail to the front of the rack with two M5 washers and
two M5 screws.
5. Repeat Steps 3 and 4 for the other rail.
1
2
Figure4. Installing the Rail Kit