INSTALLATION

W A R N I N G

The RPO/ROO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.

To install the RPO or ROO switch:

1.Verify that the UPS is off and unplugged.

2.Unscrew and remove the RPO/ROO connector from the RPO/ROO port on the UPS rear panel.

3.Refer to the following table to plan the RPO or ROO behavior:

Contact

RPO

 

 

ROO*

 

 

 

 

 

Open

UPS shuts down, the

 

indicator

UPS shuts down

 

 

 

 

 

illuminates

 

 

 

 

 

 

 

 

Closed

Normal operation

 

To return to normal operation,

 

deactivate the remote external

 

contact and restart the UPS by

 

pressing the

button

UPS starts up (UPS connected to AC power and AC power is available)

NOTE The local button overrides the ROO function.

4.Connect isolated, normally-closed, dry contacts (rated to handle

60 Vdc maximum, 30 Vac RMS maximum, and 20 mA maximum). Use stranded, non-shielded wiring, size 0.75 mm2–0.5 mm2 (18–20 AWG).

5.Reinstall the RPO/ROO connector to the RPO/ROO port.

6.Verify that the externally-connected RPO switch is not activated to enable power to the UPS output receptacles.

7.Plug the UPS power cord into a power outlet.

8.Press and hold the button until you hear the UPS beep (approximately one second).

9.Activate the external RPO or ROO switch to test the function. Verify the status change on the UPS front panel.

10.RPO only. De-activate the external RPO switch and restart the UPS.