SPECIFICATIONS
EATONPowerware®5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S164201730Rev 2
www.powerware.com
52
Table11. High-Voltage Model Specifications
ModelNumber PowerLevels
(Ratedat
NominalInputs)
ACInput Outputon Battery Power
Nominal
Voltage Voltage
Range1Frequency
Range2Voltage3Frequency
PW5130i1250-XL2U 1250VA, 1150W
220–240V 160–294V 47–70Hz (50 Hz
system),
56.5–70Hz (60 Hz
system)
230V
(+6/-10%) 50/60Hz
±0.1%
PW5130i1750-XL2U 1750VA, 1600W
PW5130i2500-XL2U 2500VA, 2250W
PW5130i3000-XL2U
3000VA, 2700W
PW5130i3000-XL3U
PW5130G3000-XL2U 3000VA, 2700W 208V 160–263V 208V
(+6/-10%)
1Thehigh and low thresholds can be adjusted using the UPS Configuration tool (see page 43).
2Upto 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).
3Adjustableto 100V (10% derating of output power) 120/127V.
Table12. Weights and Dimensions
Low-VoltageModel Number Dimensions(WxHxD) Weight
PW5130L1250-XL2U 440×86×509mm
17.3×3.4×20.0
24.6kg (54.3 lb)
PW5130L1750-XL2U 26.3kg (58.0 lb)
PW5130L2500-XL2U 440×86×634mm
17.3×3.4×25.0
34.7kg (76.4 lb)
PW5130L3000-XL2U 35.3kg (77.9 lb)
PW5130L3000-XL3U 440×131×484mm
17.3×5.2×19.033.8kg (75.5 lb)
High-VoltageModel Number Dimensions(WxHxD) Weight
PW5130i1250-XL2U 440×86×509mm
17.3×3.4×20.024.3kg (53.6 lb)
PW5130i1750-XL2U
PW5130i2500-XL2U 440×86×634mm
17.3×3.4×25.033.8kg (74.5 lb)
PW5130i3000-XL2U
PW5130G3000-XL2U 440×86×634mm
17.3×3.4×25.035.3kg (77.9 lb)
PW5130i3000-XL3U 440×131×484mm