SPECIFICATIONS
EATONPowerware®5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S164201730Rev 2
www.powerware.com
54
Table14. Environmental and Safety
LowVoltage Models HighVoltage Models
OperatingTemperature 0°Cto 40°C (32°F to 104°F)
StorageTemperature -25°C to 40°C (-13°F to 104°F)
RelativeHumidity Storage: 10–95% noncondensing
Operating: 20–95% noncondensing
AudibleNoise Lessthan 40 dBA Normal mode, typical load
Lessthan 45 dBA (50 dBA for 3000 VA) Battery mode
SurgeSuppression ANSIC62.41 Category B, IEC 61000-4-5
SafetyConformance UL1778, UL 497A;
CSAC22.2, No. 107.1;
NOM-019-SCFI
UL1778, UL 497A (data line only);
CSAC22.2, No. 107.1;
EN62040-1-1, IEC 60950-1, IEC 50091-1-1
AgencyMarkings cULus, cUL cTUVus, CE
EMC FCCPart 15 Class A EN62040-2 C1, AS 62040-2 C1,
FCCPart 15 Class B
Table15. Battery
UPSConfiguration 1250VA: (4)12V, 7.2 Ah internal batteries
1750VA: (4)12V, 9 Ah internal batteries
2500VA: (6)12V, 7.2 Ah internal batteries
3000VA: (6)12V, 9 Ah internal batteries
EBMConfiguration PW5130N1750-EBM2U:48 Vdc, (2 stings of 4) 12V, 9 Ah batteries
PW5130N3000-EBM2Uand PW5130N3000-EBM3U: 72Vdc, (2 strings of 6)
12V,9 Ah batteries
Type Sealed,maintenance-free, valve-regulated, lead-acid