INSTALLATION

RPO and ROO Installation

The Powerware 5130 includes a two-position terminal (see Figure 11) that can be either left closed or configured one of two ways:

SRPO: Allows a remote contact to be used to disconnect all equipment connected to the UPS. Restarting the UPS requires manual intervention.

SROO: Allows remote action of the button to shut down the UPS.

RPO

ROO

Figure 11. RPO/ROO Connection

EATON Powerware® 5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2