TROUBLESHOOTING

Table 17. Troubleshooting Guide

Alarm or Condition

Possible Cause

Action

 

 

 

When starting the UPS with the button, all the indicators turn on once, the alarm beeps once, and

then indicator remains on.

The remote power-off (RPO)

Set the contact back to its normal position

contact has been activated to

and press the

button to restart.

shut down the UPS and now

 

 

prevents restart.

 

 

The button, μand indicators are on and all the bar graph indicators flash.

The percent load is greater than the set overload level or UPS capacity.

Check the power drawn by the connected devices and disconnect any non-priority devices. Check the overload setting.

The button and indicator

are on and all the bar graph indicators flash.

A critical overload has occurred. If utility power fails, the load will not be protected in Battery mode.

Check the power drawn by the connected devices and disconnect any non-priority devices.

The indicator is on and all the bar graph indicators flash.

A battery fault has been detected during the automatic test.

Replace the battery (see “Replacing Batteries” on page 46).

The indicator alone is on and the alarm sounds continuously.

UPS fault condition. The load is

Contact your service representative.

not supplied.

 