SPECIFICATIONS

Table 16. Battery Runtimes

Half Load

UPS Internal Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

 

 

 

 

 

 

1250 VA/575W

15 min 22 sec

58 min

1 hr 40 min

2 hr 23 min

3 hr 5 min

 

 

 

 

 

 

1750 VA/800W

9 min 35 sec

36 min 11 sec

1 hr 2 min

1 hr 29 min

1 hr 55 min

 

 

 

 

 

 

2500 VA/1125W

11 min 15 sec

55 min

1 hr 40 min

2 hr 30 min

3 hr 26 min

 

 

 

 

 

 

3000 VA/2700W

10 min 15 sec

44 min

1 hr 13 min

1 hr 41 min

2 hr 10 min

 

 

 

 

 

 

Full Load

UPS Internal Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

 

 

 

 

 

 

1250 VA/1150W

5 min

29 min 49 sec

54 min 38 sec

1 hr 19 min

1 hr 44 min

 

 

 

 

 

 

1750 VA/1600W

3 min 30 sec

16 min

28 min 30 sec

41 min

53 min 30 sec

 

 

 

 

 

 

2500 VA/2250W

3 min

23 min

42 min

1 hr 3 min

1 hr 25 min

 

 

 

 

 

 

3000 VA/2700W

3 min

17 min

32 min

47 min

1 hr 2 min

 

 

 

 

 

 

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

EATON Powerware® 5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2

55

www.powerware.com

 

Page 61
Image 61
Eaton Electrical 1250-3000 VA manual Battery Runtimes, Half Load, +1 EBM +2 EBMs +3 EBMs +4 EBMs, Full Load