SPECIFICATIONS
Table 16. Battery Runtimes
Half Load | UPS Internal Batteries | +1 EBM | +2 EBMs | +3 EBMs | +4 EBMs |
|
|
|
|
|
|
1250 VA/575W | 15 min 22 sec | 58 min | 1 hr 40 min | 2 hr 23 min | 3 hr 5 min |
|
|
|
|
|
|
1750 VA/800W | 9 min 35 sec | 36 min 11 sec | 1 hr 2 min | 1 hr 29 min | 1 hr 55 min |
|
|
|
|
|
|
2500 VA/1125W | 11 min 15 sec | 55 min | 1 hr 40 min | 2 hr 30 min | 3 hr 26 min |
|
|
|
|
|
|
3000 VA/2700W | 10 min 15 sec | 44 min | 1 hr 13 min | 1 hr 41 min | 2 hr 10 min |
|
|
|
|
|
|
Full Load | UPS Internal Batteries | +1 EBM | +2 EBMs | +3 EBMs | +4 EBMs |
|
|
|
|
|
|
1250 VA/1150W | 5 min | 29 min 49 sec | 54 min 38 sec | 1 hr 19 min | 1 hr 44 min |
|
|
|
|
|
|
1750 VA/1600W | 3 min 30 sec | 16 min | 28 min 30 sec | 41 min | 53 min 30 sec |
|
|
|
|
|
|
2500 VA/2250W | 3 min | 23 min | 42 min | 1 hr 3 min | 1 hr 25 min |
|
|
|
|
|
|
3000 VA/2700W | 3 min | 17 min | 32 min | 47 min | 1 hr 2 min |
|
|
|
|
|
|
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
EATON Powerware® 5130 Rack/Tower UPS | 55 |