ADDITIONALUPS FEATURES
EATONPowerware®5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S164201730Rev 2
www.powerware.com
43
Customizing the UPS with the UPS Configuration Tool

To customize the UPS settings:

1. Download the UPS Configuration tool from www.powerware.com.

2. Follow the on-screen instructions for the Powerware 5130.

It is possible to modify the settings listed below (detailed

comments are available in the UPS Configuration tool).

Table5. Main Output Options

Function FactorySetting OtherAvailable Settings
Low-VoltageModels. Output voltage on
batterypower
120Vac 100/120/127Vac
High-VoltageModels. Output voltage on
batterypower
230Vac 200/208/220/240Vac
PW5130G3000-XL2UModels. Output
voltageon battery power
208V
AllModels. Overload alarm threshold 105% 30/50/70%

Table6. Voltage Threshold Options

Low-VoltageModel Function Factory Setting OtherAvailable Settings
Highthreshold for transfer to battery 151Vac ±3% 141–153 Vac
Lowthreshold for transfer to battery 89Vac ±3% 89–94 Vac
Faderactivation threshold 132Vac ±3% 127–138 Vac
Boosteractivation threshold 102Vac ±3% 92–108 Vac
Maximuminput-voltage range Disabled Enabled1
High-VoltageModel Function FactorySetting OtherAvailable Settings
Highthreshold for transfer to battery 294Vac 271–294Vac
Lowthreshold for transfer to battery 160 Vac 160–180Vac
Faderactivation threshold 265Vac 244–265Vac
Boosteractivation threshold 184Vac 184–207Vac
Maximuminput-voltage range Disabled Enabled2
1Lowthreshold for transfer to battery is 70V.
2Lowthreshold for transfer to battery is 150V.