ADDITIONAL UPS FEATURES

Table 6. Voltage Threshold Options (continued)

PW5130G3000-XL2U Function

Factory Setting

Other Available Settings

 

 

 

High threshold for transfer to battery

263 Vac

 

 

 

Low threshold for transfer to battery

160 Vac

 

 

 

Fader activation threshold

229 Vac

 

 

 

Booster activation threshold

177 Vac

 

 

 

Maximum input-voltage range

Disabled

Enabled2

2 Low threshold for transfer to battery is 150V.

 

 

Table 7. UPS Sensitivity Options

Function

Factory Setting

Other Available Settings

 

 

 

UPS-sensitivity level

Normal

High or low

 

 

 

Table 8. UPS On/Off Options

Function

Factory Setting

Other Available Settings

 

 

 

Automatic start

Enabled

Disabled

 

 

 

Cold start

Enabled

Disabled

 

 

 

Forced shutdown

Enabled

Disabled

 

 

 

Energy-savings mode

Disabled

Enabled

 

 

 

UPS ON/OFF controlled by software

Enabled

Disabled

 

 

 

Battery level before restart

0%

0–100%

 

 

 

Table 9. Battery Options

Function

Factory Setting

Other Available Settings

 

 

 

Battery-test intervals

Low-battery warning

Battery protection against deep discharge

Audio alarm

Additional battery module

Weekly

No test / daily test / monthly test

20%

0–100%

 

 

Enabled

Disabled

 

 

Enabled

Disabled

 

 

Automatic detection of number of

For specific batteries, 25–81 Ah

battery modules

 

44EATON Powerware® 5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2 www.powerware.com

Page 50
Image 50
Eaton Electrical 1250-3000 VA manual UPS Sensitivity Options, UPS On/Off Options, Battery Options