Epsilon Eb Digital Servo Drive Installation Manual

Line Fusing and Wire Size

You must incorporate over current protection for the incoming AC power with the minimum rating shown below. Control Techniques recommends Bussman type: LPN or equivalent.

 

Drive Model

 

External AC Line Fuse

 

Recommended Minimum AC/PE Line

 

 

 

 

 

Wire Gauge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eb-202

 

 

LPN 6 Amp

 

 

 

16 AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eb-203

 

 

LPN 8 Amp

 

 

 

16 AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eb-205

 

 

LPN 12 Amp

 

 

 

16 AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

Frequenc

 

Input Current

Inrush Current (Amps)

 

 

Drive Model

 

 

(Amps RMS) at

 

 

 

(VAC)

y (Hz)

 

full drive output

1 st Cycle

2nd Cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

current

 

 

 

 

 

Eb-202

 

 

 

 

 

 

4.3

140 (2 ms)

 

20 (2 ms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eb-203

 

240 / 1 Ø

47 - 63

 

 

6.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eb-205

 

 

 

 

 

 

10.8

140 (5 ms)

 

30 (2 ms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Epsilon Only

This inrush current specification assumes the drive has been powered off for at least eight minutes at 40° C ambient or five minutes at 25° C ambient. If this amount of time has not elapsed since power off, the inrush current will be higher.