MODEL 54e pH/ORP | SECTION 5.0 |
| SOFTWARE CONFIGURATION |
TABLE 5-1. pH Settings List (continued)
ITEM | RANGES | FACTORY SETTINGS | USER SETTINGS | |
2b. Output 1 Setup (PID) |
|
|
|
|
(a) Setpoint |
| 7 pH | _______ | |
(b) Proportional |
| 100.0% | _______ | |
(c) Integral |
| 0 sec | _______ | |
(d) Derivative |
| 0.0% | _______ | |
(e) LRV (4 mA) |
| 2 pH | _______ | |
(f) URV (20 mA) |
| 0 pH | _______ | |
3. Output 2 Control |
|
|
|
|
(a) Output 2 Measurement | Process/Temp/Glass Imp/Ref Imp | Temperature | _______ | |
(b) Output 2 Control Mode | Normal/PID |
| Normal | _______ |
4a. Output 2 Setup (Normal) |
|
|
|
|
(a) Current Range |
| _______ | ||
(b) Dampening |
| 0 Sec | _______ | |
(c) Hold Mode | Last value/Fixed value |
| Last value | _______ |
(d) Fixed Hold Value (if (c) Fixed) |
| 21 mA | _______ | |
(e) Fault value |
| 22 mA | _______ | |
4b. Output 2 Setup (PID) |
|
|
|
|
(a) Setpoint |
| 7 pH | _______ | |
(b) Proportional |
| 100.0% | _______ | |
(c) Integral |
| 0 sec | _______ | |
(d) Derivative |
| 0.0% | _______ | |
(e) LRV (4 mA) |
| 2 pH | _______ | |
(f) URV (20 mA) |
| 0 pH | _______ | |
5. Hold (Outputs and Relays) | Disable/Enable/ 20 min timeout | Disable feature | _______ | |
C. Alarms (Section 5.7) |
|
|
|
|
1. Alarm 1 Control |
|
|
|
|
(a) Activation Method | Process/Temp |
| Process | _______ |
(b) Alarm 1 Control Mode | Normal/TPC |
| Normal | _______ |
2a. Alarm 1 Setup (Normal) |
|
|
|
|
(a) Configuration | Low alarm/High alarm/Off |
| Low | _______ |
(b) Hysteresis (deadband) | 0 - 5.00 pH |
| 0.01 pH | _______ |
(c) Delay Time |
| 0 sec | _______ | |
(d) Relay Fault | Open/Closed/None |
| None | _______ |
2b. Alarm 1 Setup (TPC) |
|
|
|
|
(a) Setpoint |
| 7 pH | _______ | |
(b) Proportional |
| 100.0% | _______ | |
(c) Integral |
| 0 sec | _______ | |
(d) Derivative |
| 0.0% | _______ | |
(e) Time Period |
| 30 sec | _______ | |
(f) LRV (100% On) |
| 2 pH | _______ | |
(g) URV (100% Off) |
| 0 pH | _______ | |
(h) Relay Fault | None/Open/Closed |
| None | _______ |
3. Alarm 2 Control |
|
|
|
|
(a) Activation Method | Process/Temp |
| Process | _______ |
(b) Alarm 2 Control Mode | Normal/TPC |
| Normal | _______ |
4a. Alarm 2 Setup (Normal) |
|
|
|
|
(a) Configuration | Low alarm/High alarm/Off |
| High | _______ |
(b) Hysteresis (deadband) | 0 - 5.00 pH |
| 0.01 pH | _______ |
(c) Delay Time |
| 0 sec | _______ | |
(d) Relay Fault | Open/Closed/None |
| None | _______ |
4b. Alarm 2 Setup (TPC) |
|
|
|
|
(a) Setpoint |
| 7 pH | _______ | |
(b) Proportional |
| 100.0% | _______ | |
(c) Integral |
| 0 sec | _______ | |
(d) Derivative |
| 0.0% | _______ | |
(e) Time Period |
| 30 sec | _______ | |
(f) LRV (100% On) |
| 2 pH | _______ | |
(g) URV (100% Off) |
| 0 pH | _______ | |
(h) Relay Fault | None/Open/Closed |
| None | _______ |
|
|
|
|
|
Continued on the following page
23