X70^

=

Clear value

 

 

0

= condition no longer met

 

 

1

= clear with output off

 

 

2

= clear with output on

 

 

3

= clear with no threshold

 

 

4

= clear with standby threshold

 

 

5

= clear with full threshold

 

 

6

= clear with any change

 

 

7

= manual

X70&

=

Relay polarity

 

 

0

= normally open

 

 

1

= normally closed

X70*

= Time to hold alarm active before canceling

 

 

0

= never times out

 

 

1-7= 1 to 7 minutes

X70(

=

On timed value

 

 

00-15(in 250 ms increments)

X71)

=

Off timed value

 

 

00-15(in 250 ms increments)

X71! =

Day of the week

 

 

1

= Sunday

 

 

2

= Monday

 

 

3

= Tuesday

 

 

4

= Wednesday

 

 

5

= Thursday

 

 

6

= Friday

 

 

7

= Saturday

X71@

=

Time in minutes (0-1440)

 

 

0

= 00:00 am (midnight)

 

 

1440 = clear schedule

 

 

Example: 1439 = 11:59

Use the following formula (in 24-hour time format): (hour x 60) + minutes = time in minutes

IPL T PCS4 • SIS Programming and Control 48

Page 54
Image 54