Extron electronic manual Rack mounting procedure, Mounting the IPL T PCS4 on a Rack Shelf

Models: IPL T PCS4 IPL T PCS4i

1 69
Download 69 pages 31.92 Kb
Page 63
Image 63
Rack mounting procedure

Circuit overloading — When connecting the equipment to the supply circuit, consider the effect that circuit overloading might have on overcurrent protection and supply wiring. Consider equipment nameplate ratings when addressing this concern.

Reliable earthing (grounding) — Maintain reliable grounding of rack-mounted equipment. Pay particular attention to supply connections other than direct connections to the branch circuit (such as the use of power strips).

Rack mounting procedure

Rack mount the interface, if desired, using the RSU 129 Universal Rack Shelf Kit (part number 60-190-01) as follows:

Half-rack

false front panel uses 2 front holes.

IPLTP

CS4

R

F

1

S

 

F

2

S

F

3

 

 

S

F

4

 

 

S

 

(2) 4-40 x 3/16" screws

S

 

ETR

 

STANDEFER

BY

ENCE

 

FULL

100 LINK ACT

Use 2 mounting holes on opposite corners.

Figure 37. Mounting the IPL T PCS4 on a Rack Shelf

1.If rubber feet have been installed on the bottom of the unit, remove them.

2.Mount the PCS4 on the rack shelf, using two 4-40 x 3/16 inch screws in opposite (diagonal) corners to secure the unit to the shelf.

3.Attach a blank panel or other units to the rack shelf.

4.Insert the shelf into the rack, aligning the holes in the shelf with those in the rack.

5.Secure the shelf to the rack using the supplied machine screws. This shelf can be mounted in the front or in the rear of the rack.

IPL T PCS4 • Reference Material 57

Page 63
Image 63
Extron electronic IPL T PCS4i manual Rack mounting procedure, Mounting the IPL T PCS4 on a Rack Shelf