Installation (for qualified installers only)

1 5

Vent Installation

In addition to the requirements below, follow the requirements provided with the vent.

Vertical Vent Requirements

Vertical Termination (part # 1291)

Use a roof flashing and storm collar

whenever passing through the roof Combustible Framing

Use the Simpson ceiling firestop (#1263) whenever passing through a ceiling (or enclosure and at every floor penetration.

10"

by

10"

Min. 1" clearance from vertical sections to combustible surfaces.

Minimum framing for fire stop

Horizontal Vent

Requirements

Minimum framing

for fire stop

Minimum

12" tall

Minimum 10" wide

Use the Travis firestop (part # 93006094) when passing through a wall. NOTE: make sure the firestop is postitioned correctly so the 3" clearance is allowed above the vent.

1" Min.

Combustible

Surfaces

3" Min.

1" Min.

Slide the vent sections together and turn 1/4 turn until the sections lock in

place.

Screws are not required to secure the vent. However, three screws may be used to secure vent sections together if desired.

High temperature sealant is recommended at the appliance starter section

connection (use high-temperature silicone or Mill-Pac® ).

If disassembly is required, at time of re-assembly check to see if the vent creates a tight fit. If it does not, apply high temperature sealant to the joints of the affected sections.

Horizontal sections require a 1/4" rise every 12" of travel

Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)