FireplaceXtrordinair 44 DV XXL EF manual Horizontal Terminations with Three Vertical Elbows

Models: 44 DV XXL EF

1 56
Download 56 pages 32.4 Kb
Page 19
Image 19

Installation (for qualified installers only)

1 9

Horizontal Terminations with Three Vertical Elbows

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.

NOTE:

• A total of three elbows must be used.

No horizontal elbows may be used (a horizontal elbow is defined as an elbow that directs the vent from a horizontal direction to another horizontal direction).

• Two 45° elbows may be substituted for two of the 90° elbows.

Horizontal sections require a 1/4" rise every 12" of travel.

The maximum vertical height is 19'.

• The maximum horizontal length is 20'.

Horizontal Elbows are

NOT ALLOWED

0feet

5feet

10feet

15feet

20'(max)

19' (max)

15feet

10feet

NOTE:

Restrictor

Restrictor positions are based upon

Position #5

lab tests. The ideal restrictor position

 

may vary slightly.

 

 

Restrictor

Position #1

19' (max)

15feet

10feet

5 feet

0 feet

0 feet

5 feet

Min. 24" Rise

Before First Elbow

0 feet

5feet

10feet

15feet

20'(max)

Travis Industries

4050114

1 0 0 - 0 1 1 4 9

Page 19
Image 19
FireplaceXtrordinair 44 DV XXL EF manual Horizontal Terminations with Three Vertical Elbows