1 2 | Installation (for qualified installers only) |
Gas Line Requirements
!The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and the requirements listed below.
!The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig, isolate the gas supply piping by closing the manual shutoff valve.
!Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
Fuel
•This fireplace is designed either for natural gas or for propane (but not for both). Check the sticker on the top of the gas control valve to make sure the correct fuel is used.
Gas Line Connection
•A manual shutoff valve is required for installation (within 3’ of the heater or inside the fireplace).
The 1" diameter access hole is located
A shutoff valve may be placed within the fireplace
The modulating remote shield may be removed to ease installation.
If the gas line is routed from the
right side, bend the flex tube 180°.
3/8" M.P.T to 1/2" O.D. Fitting (Factory installed)
Gas Control Valve
|
| |
|
| |
The included |
|
|
fitting accepts a | 10" Flex Tube | |
3/8" M.P.T. or | (shipped with the fireplace - min. bending radius is 3/4") | |
1/2" F.P.T. |
|
|
Gas Inlet Pressure: |
| Standard Input Pressure |
|
| |
Natural Gas | 7" W.C. (1.74 kPA) | |
Propane |
| 13" W.C. (2.73 kPA) |
•If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
•The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.