Heat & Glo LifeStyle XLR-N-CE K. Install Horizontal Termination Cap, 17 Venting through the wall

Models: XLR-N-CE XLR-PB-CE

1 65
Download 65 pages 6.02 Kb
Page 40
Image 40
K. Install Horizontal Termination Cap

K. Install Horizontal Termination Cap

WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent.

3,8 cm minimum overlap of flue telescoping section is required.

Failure to maintain overlap may cause overheating and fire.

Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.

Flash and seal as appropriate for siding material at outside edges of cap.

When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current local or national codes and refer to Section 6 of this manual.

CAUTION! Risk of Burns! Local codes may require in- stallation of a cap shield to prevent anything or anyone from touching the hot cap.

Note: When using termination caps with factory-supplied heat shield attached, no additional wall shield firestop is required on the exterior side of a combustible wall.

HEAT SHIELD OR

HEAT SHIELD

EXTENDED

3,8 CM MIN.

HEAT SHIELD

OVERLAP

WALL SHIELD

 

FIRESTOP

 

SLIP SECTION

 

CAN BE EXTENDED

 

INNER VENT

SHEATHING

OUTER VENT

 

INTERIOR

EXTERIOR

Figure 10.17 Venting through the wall

 

40

Heat & Glo • XLR-N-CE, XLR-PB-CE2198-900 Rev. J • 5/12

Page 40
Image 40
Heat & Glo LifeStyle XLR-N-CE, XLR-PB-CE manual K. Install Horizontal Termination Cap, 17 Venting through the wall