WTC 600 LP / MP | DESCRIPTION |
2.3.1.7
If required, the WTC 600 PI
NOTE A
CAUTION Observe mechanical protection as well as protection of the connection cable against water!
1
Figure 6 WTC 600 PI
2.3.2Safety Installations
Emergency Stop
The emergency stop switch (7/4) (main switch) is located on the side of the switch box.
RC Protective Switch
RC protective switch (external): i ≤ 30 mA
Circuit Breaker
Automatic circuit breaker (7/3) 10 A for power limitation of the power outlets, etc
Motor Protection Switch
The motor protection switch (7/2) is
WTC 600 | Nominal output | Actual power | Motor protection |
| RO pump | consumption | switch setting |
|
|
|
|
LP 400 V | 2.2 kW | 1.5 kW | 4 A |
|
|
|
|
MP 400 V | 2.2 kW | 2.2 kW | 5.1 A |
|
|
|
|
|
|
|
|
LP 230V | 2.2 kW | 1.5 kW | 10 A |
|
|
|
|
MP 230 V | 2.2 kW | 2.2 kW | 14 A |
|
|
|
|
Table 2 Setting of motor protection switch
Service Handbook 08.2004 | 15 |