MAINTENANCE | WTC 600 LP / MP |
4.5.3Malfunctions of the RO Control and Metering Pump
Indication | Malfunction | Cause | Corrective Action | Chap./ |
|
|
|
| Fig. |
Indication of RO | Fuse defective |
| Have replaced by | ETL, |
control dark |
|
| electrician | diagram |
|
|
|
| in switch |
|
|
|
| cabinet |
|
|
|
|
|
| Short circuit, |
| Replace defective parts |
|
| general |
|
|
|
| Solenoid valve |
| Replace defective parts | ETL |
| defective |
|
|
|
|
|
|
|
|
| Motor winding |
| Replace defective parts | ETL |
| defective |
|
|
|
|
|
|
|
|
Water level in | Pump does not | Suction line untight | Retighten screwed | ETL |
container is | draw in |
| fittings. Replace |
|
constant for |
|
| suction line |
|
days |
|
|
|
|
|
|
|
|
|
|
| Suction line | Flush or replace |
|
|
| clogged | suction line |
|
|
|
|
|
|
|
| Crystals, debris in | Clean valves | 4.2 |
|
| the valves |
|
|
|
| (metering head) |
|
|
|
| Membrane torn or | Replace membrane | 4.2 |
|
| membrane push- |
|
|
|
| rod torn out |
|
|
|
|
|
|
|
| Pump does not | Air in the suction | Bleed pump |
|
| meter | line and in the |
|
|
|
| metering head |
|
|
|
|
|
|
|
|
| Lift adjustment a | While the pump is |
|
|
| zero | running, turn in “+” |
|
|
|
| direction (adjustment |
|
|
|
| values, see 3.3.1) |
|
|
|
|
|
|
|
| Crystals, debris in | Clean valves | 4.2 |
|
| the valves |
|
|
|
| (metering head) |
|
|
|
|
|
|
|
|
| Valves not | Check correct |
|
|
| mounted correctly | valves and correct, |
|
|
|
| if required (direction of |
|
|
|
| arrow!) |
|
|
|
|
|
|
|
| Injection fitting | Check direction of flow |
|
|
| blocked | and correct, if required, |
|
|
|
| or eliminate plug |
|
|
|
| (direction of arrow!) |
|
|
|
|
|
|
Table 30 |
|
|
|
|
58 | Service Handbook 08.2004 |