APPENDIX | WTC 600 LP / MP |
4.4.3Setting menu
The calibration menu is used to adjust the sensors. The following functions are available:
Menu point: | Function: | |
1 | t Cy LIM | Numerical editing of t delay LIM |
2 | t Cy alarm | Numerical editing of t delay aaLIM |
3 | t lack of pressure | Numerical editing of t delay lack of pressure |
4 | t delay at start | Numerical editing of t delay at start |
5 | t press. availabe | Numerical editing of t pressure failure |
6 | t disc. rinse | Numerical editing of t rinse |
7 | t rinse.interval | Numerical editing of t rinse interval |
8 | t concentrate | Numerical editing of t concentrate |
9 | t disposal | Numerical editing of t disposal |
10 t maintenance | Numerical editing of t maintenance | |
11ps failure alarm | Selection of ps acknowledgment | |
12 ps concentrate | Selection of ps concentrate | |
13 ps type of tank | Selection of ps tank type | |
14 inputs | Setting of input types (valve with open rest pos./opener) | |
15 ps language | Selection of ps language | |
16 system reset | As soon as this function is | |
|
| the internal hours meter will be deleted (set to 0) |
4.4.4Diagnosis menu
The diagnosis allows direct display/manipulation of the input/output conditions for testing purposes.
ATTENTION!!! Under these conditions, failure detection is not active.
Menu point: | Function: |
1 digital input | Display of the current conditions of the digital inputs (see item 2.3). |
| Display is like a multiselection, but with the difference that the conditions |
| of the arguments cannot be set - they depend on the input conditions. |
2 digital output | Manipulation of the digital circuit outputs (see item 2.3) by means of a |
| multiselection. |
3 lights | Manipulation of the lights (item 4.1.1) by means of a multiselection. |
4 Cy permeate | Permanent display of the current permeate conductivity. This display can |
| be cancelled by actuating one of the keys. |
5 temp. permeate | Permanent display of the current permeate temperature. This display can |
| be cancelled by actuating one of the keys. |
88 | Service Handbook 08.2004 |