APPENDIX |
| WTC 600 LP / MP |
t rinse interval | function: | Time after which a DISCONTINUOUS RINSE |
|
| process is started provided that the control |
|
| system was during that time in the operating |
|
| condition RINSE INTERVAL. |
| right of access: | technician |
| possible setting: | |
t concentrate | function: | Duration of a CONCENTRATE |
|
| DISPLACEMENT/FLUSH process at the end of |
|
| a PRODUCTION (TANK FULL active). |
| right of access: | technician |
| possible setting: | |
t min disposal | funtion: | Minimum duration of a DISPOSAL process at the |
|
| beginning of a PRODUCTION. This is the |
|
| minimum time after which the unit passes to |
|
| PRODUCTION if the value drops below LIM. |
| right of access: | technician |
| possible setting: | |
|
| Attention: the set value must be less than t max |
|
| disposal. (Pay attention to units) |
t max disposal | function: | Maximum duration of a DISPOSAL process. This |
|
| is the maximum time after which the value has to |
|
| be below LIM, otherwise a failure message will be |
|
| given. |
| right of access: | technician |
| possible setting: | |
|
| Attention: the set value must be greater than |
|
| t min disposal (Pay attention to units!) |
t maintenance | function: | Operating time (hour meter) after which a signal |
|
| is given that maintenance has to be carried out |
|
| (flashing OPERATION). |
| right of access: | technician |
| possible setting: | |
|
| Attention: zero setting means that no |
|
| maintenance message is given. |