TP-6880 10/1414 Section1 DescriptionsandService Views
RDC2 Controller Features
DSix-button keypad
dOFF,AUTO, and RUN pushbuttons
dSelect and arrow buttons for access to system
configuration and adjustment menus
DLED indicators for OFF,AUTO, and RUN modes
DLED indicators for utility power and generator set
source availability and ATS position (Model RXT
transfer switch required)
DLCD display
dTwolines x 16 characters per line
dBacklit display with adjustable contrast for
excellent visibility in all lighting conditions
DScrolling system status display
dGenerator set status
dVoltageand frequency
dEngine temperature
dOil pressure
dBattery voltage
dEngine runtime hours
DDate and time displays
DSmart engine cooldown senses engine temperature
DDigital isochronous governor to maintain
steady-state speed at all loads
DDigital voltage regulation: ±0.5% RMS no-load to
full-load
DAutomatic start with programmed cranking cycle
DProgrammable exerciser can be set to start
automatically on any future day and time, and run
every week or every two weeks
DExercise modes
dUnloaded weekly exercise with complete system
diagnostics
dUnloaded full-speed exercise
dLoaded full-speed exercise (Model RXT ATS
required)
DFront-access mini USB connector for SiteTecht
connection or the Kohler USB utility
DIntegral Ethernet connector for KohlerrOnCuer
Plus
DBuilt-in 2.5 amp battery charger
DRemote two-wire start/stop capability for optional
connection of Model RDT or RSB transfer switches
DDiagnostic messages
dDisplays diagnostic messages for the engine,
generator,Model RXT transfer switch,
programmable interface module (PIM), and load
control module (LCM) or load shed kit
dOver 70 diagnostic messages can be displayed
DMaintenance reminders
DSystem settings
dSystem voltage, frequency,and phase
dVoltageadjustment
dMeasurement system, English or metric
DATSstatus (Model RXT ATS required)
dSource availability
dATSposition (normal/utility or
emergency/generator)
dSource voltage and frequency
DATScontrol (Model RXT ATS required)
dSource voltage and frequency settings
dEngine start time delay
dTransfertime delays
dVoltagecalibration
dFixed pickup and dropout settings
DProgrammable Interface Module (PIM) status
displays
dInput status (active/inactive)
dOutput status (active/inactive)
DLoad control module (LCM) or load shed kit menus
dLoad status
dTestfunction