2.3.7Automatic Operation with Other Transfer Switches
If a transfer switch other than the Model RXT (such as a Kohler Model RDT or RSB) is used, the engine start contacts from the ATS must be connected to engine start leads 3 and 4 on the generator set.
The controller must be in AUTO mode to respond to remote start/stop signals from an ATS or remote switch. Press the AUTO button to put the controller into automatic mode.
Automatic Start
The engine start contacts on the ATS close to signal the generator set to start, and remain closed while the generator set is running.
Automatic Stop
The engine start contacts on the ATS open to signal the generator set to stop.
2.4 Exercise
The RDC2 and DC2 controllers can be set to automatically run the generator set at the same time and day each week. Exercising the generator set weekly or every two weeks is required to keep the engine and alternator in good operating condition.
Three exercise modes are available: unloaded cycle, unloaded full speed, and loaded full speed. See Sections 2.4.2 through 2.4.4 for information about the exercise modes. A loaded exercise can be set at the RDC2 controller only if a Model RXT transfer switch is connected.
Note: With transfer switches other than the Model RXT, it is possible to have two exercise settings (one unloaded exercise set at the generator set controller, and another exercise set at the ATS controller). If the exercise times overlap, the ATS exercise setting takes priority.
If a transfer switch other than the Model RXT is used, refer to the instructions provided with the transfer switch to set a loaded exercise at the ATS, if desired.
2.4.1Setting the Exerciser
When power is applied to the RDC2 controller (that is, when the battery is connected), you will be prompted to set the date and time, and then to set the exerciser.
The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. See Section 3.5 for
more detailed instructions to change settings on the RDC2. See Section 3.6 for more detailed instructions to set the exerciser or change the exercise settings.
The DC2 controller does not prompt you to set the exerciser. See Section 4.5 for instructions to set the exerciser on the DC2.
2.4.2Unloaded Cycle Exercise with Complete System Diagnostics
An unloaded exercise runs the generator set without signalling the transfer switch to transfer the electrical load from the utility source to the generator set. The Unloaded Cycle exercise with diagnostics is the recommended exercise mode and is the default exercise setting.
The Unloaded Cycle exercise runs the engine for 20 minutes in the cycle shown in Figure
DRuns at reduced speed for 10 minutes to warm up and exercise the engine.
D Ramps up and runs at full speed for 3 minutes. Engine diagnostics are performed during this
D Ramps down and runs at reduced speed for 5 minutes to cool down the engine before shutting down automatically.
Speed, RPM |
| 3 min. |
|
| 1 min. | 1 min. | |
Engine | 10 min. |
| 5 min. |
|
| ||
| Engine | Cooldown | |
| Exercise | Diagnostics |
|
Figure 2-1 Unloaded Exercise Cycle
22 Section 2 Generator Set Operation |