| Warning (W) or |
|
|
Fault Message | Shutdown (SD) | Condition | Check |
|
|
|
|
AC Sens Loss | W (1 sec.) | AC sensing lost. In Auto mode, generator output | Contact an authorized |
| SD (3 sec.) * | AC sensing is lost. Detection begins 10 seconds | distributor/dealer for service. |
| after crank disconnect. |
| |
|
|
| |
|
| Warning: after 1 second if no output detected |
|
|
| after crank disconnect. |
|
|
| Shutdown: after 3 seconds if voltage was |
|
|
| present and then lost. |
|
|
|
|
|
Accy PwrOver | W | Accessory Power Overload. An over current fault | Contact an authorized |
Warning |
| (short circuit) on the accessory controller power | distributor/dealer for service. |
|
| output. |
|
|
|
|
|
Alt Protect | SD | High generator current has been detected. The | Reduce the load. |
|
| generator set shuts down to protect the |
|
|
| alternator from damage caused by overheating |
|
|
| the windings (10RESV and 12RESV only). |
|
|
|
|
|
ATS ComError | W | ATS communication error. Warning is displayed | Check communication wiring between |
|
| if ATS interface connection is lost. | transfer switch interface board and |
|
| See Section 2.5.3. | generator set. |
|
|
|
|
ATS PhaseRot | W | ATS phase rotation mismatch. Transfer switch | Correct the ATS connection. Refer to |
|
| phase rotation does not match, ATS will not | the ATS Installation manual, wiring |
|
| transfer. | diagrams, and labels on the transfer |
|
|
| switch. |
|
|
|
|
Aux Input | SD * | Auxiliary input. An optional | Check |
|
| input is closed. (Digital input from optional PIM.) |
|
|
|
|
|
Batt Chg Flt | W | Battery charger fault. Input to PIM from an | Check external battery charger. |
|
| external battery charger (not the |
|
|
| charger). |
|
Battery High | W | Engine starting battery voltage rises above 16 | Check the battery rating and |
|
| VDC for more than 10 seconds. Inhibited during | condition. |
|
| the engine crank cycle. | Check the battery charger operation. |
|
| Clears when the battery voltage returns to an | |
|
|
| |
|
| acceptable level. |
|
|
|
|
|
Battery Low | W | Engine starting battery voltage falls below 12.5 | Check the battery rating and |
|
| VDC for more than 90 seconds when the engine | condition. |
|
| is not running. Not operative during the engine | Check the battery charger operation. |
|
| crank cycle. | |
|
| Charge or replace the battery. | |
|
| Clears when the battery voltage returns to an | |
|
|
| |
|
| acceptable level. |
|
|
|
|
|
Battery CrLo | W | Engine starting battery voltage falls below 11 | Check the battery rating and |
Warning |
| Volts for more than 10 seconds. Inhibited during | condition. |
|
| the engine crank cycle. | Check the battery charger operation. |
|
| Clears when the battery voltage returns to an | |
|
| Charge or replace the battery. | |
|
| acceptable level. | |
|
|
| |
|
|
|
|
Eng Speed | SD * | Engine speed exceeds 115% of the normal | Contact an authorized |
High |
| running speed for more than 0.3 seconds. | distributor/dealer for service. |
|
|
|
|
Eng Speed Low | SD * | Engine speed drops below 85% of the normal | Reduce the load. |
|
| running speed for more than 3 seconds. | Contact an authorized |
|
|
| |
|
|
| distributor/dealer for service. |
|
|
|
|
Exer Not Sch | W | Exercise not scheduled. No exercise is | See Section 3.6 or 4.5 for instructions |
|
| scheduled on the controller. | to set the exerciser. |
|
|
|
|
* Engine cooldown runs before shutting down.
Section 2 Generator Set Operation 25 |