Warning (W) or

 

 

Fault Message

Shutdown (SD)

Condition

Check

 

 

 

 

AC Sens Loss

W (1 sec.)

AC sensing lost. In Auto mode, generator output

Contact an authorized

 

SD (3 sec.) *

AC sensing is lost. Detection begins 10 seconds

distributor/dealer for service.

 

after crank disconnect.

 

 

 

 

 

 

Warning: after 1 second if no output detected

 

 

 

after crank disconnect.

 

 

 

Shutdown: after 3 seconds if voltage was

 

 

 

present and then lost.

 

 

 

 

 

Accy PwrOver

W

Accessory Power Overload. An over current fault

Contact an authorized

Warning

 

(short circuit) on the accessory controller power

distributor/dealer for service.

 

 

output.

 

 

 

 

 

Alt Protect

SD

High generator current has been detected. The

Reduce the load.

 

 

generator set shuts down to protect the

 

 

 

alternator from damage caused by overheating

 

 

 

the windings (10RESV and 12RESV only).

 

 

 

 

 

ATS ComError

W

ATS communication error. Warning is displayed

Check communication wiring between

 

 

if ATS interface connection is lost.

transfer switch interface board and

 

 

See Section 2.5.3.

generator set.

 

 

 

 

ATS PhaseRot

W

ATS phase rotation mismatch. Transfer switch

Correct the ATS connection. Refer to

 

 

phase rotation does not match, ATS will not

the ATS Installation manual, wiring

 

 

transfer.

diagrams, and labels on the transfer

 

 

 

switch.

 

 

 

 

Aux Input

SD *

Auxiliary input. An optional customer-connected

Check customer-supplied equipment.

 

 

input is closed. (Digital input from optional PIM.)

 

 

 

 

 

Batt Chg Flt

W

Battery charger fault. Input to PIM from an

Check external battery charger.

 

 

external battery charger (not the built-in battery

 

 

 

charger).

 

Battery High

W

Engine starting battery voltage rises above 16

Check the battery rating and

 

 

VDC for more than 10 seconds. Inhibited during

condition.

 

 

the engine crank cycle.

Check the battery charger operation.

 

 

Clears when the battery voltage returns to an

 

 

 

 

 

acceptable level.

 

 

 

 

 

Battery Low

W

Engine starting battery voltage falls below 12.5

Check the battery rating and

 

 

VDC for more than 90 seconds when the engine

condition.

 

 

is not running. Not operative during the engine

Check the battery charger operation.

 

 

crank cycle.

 

 

Charge or replace the battery.

 

 

Clears when the battery voltage returns to an

 

 

 

 

 

acceptable level.

 

 

 

 

 

Battery CrLo

W

Engine starting battery voltage falls below 11

Check the battery rating and

Warning

 

Volts for more than 10 seconds. Inhibited during

condition.

 

 

the engine crank cycle.

Check the battery charger operation.

 

 

Clears when the battery voltage returns to an

 

 

Charge or replace the battery.

 

 

acceptable level.

 

 

 

 

 

 

 

Eng Speed

SD *

Engine speed exceeds 115% of the normal

Contact an authorized

High

 

running speed for more than 0.3 seconds.

distributor/dealer for service.

 

 

 

 

Eng Speed Low

SD *

Engine speed drops below 85% of the normal

Reduce the load.

 

 

running speed for more than 3 seconds.

Contact an authorized

 

 

 

 

 

 

distributor/dealer for service.

 

 

 

 

Exer Not Sch

W

Exercise not scheduled. No exercise is

See Section 3.6 or 4.5 for instructions

 

 

scheduled on the controller.

to set the exerciser.

 

 

 

 

* Engine cooldown runs before shutting down.

TP-6880 10/14

Section 2 Generator Set Operation 25

Page 25
Image 25
Kohler 8/10/12RESVL manual Fault Message Shutdown SD Condition Check