4.2.3LCD Display
The controller is equipped with a
When a fault or warning condition exists, the controller will show the corresponding message. See Section 2.5 for more information on fault and warning messages.
The display backlight turns off after about a minute of no activity. The backlight turns on when a button is pressed or when the generator set starts.
Active Alert (if any)
Running
ATS: Normal *
Voltage: 240V
Freq: 60.0Hz
Engine: 123F
Oil Pressure: OK
Battery 12.3V
Runtime: 12345.6 h
Next Exercise: 7d 6h 42m
OnCue Status:
Disconnected [
Sample data shown.
* Model RXT ATS required
[ OnCue status is displayed only if OnCue password has been reset.
Figure 4-5 Status Displays, Generator Running
Active Alert (if any)
Genset State
Standby
Battery 12.3V
Runtime: 12345.6 h
Next Exercise: 7d 6h 42m
Next Maint:
123h or 12months
OnCue Status:
Disconnected
Sample data shown.
[ OnCue status is displayed only if OnCue password has been reset.
Figure 4-6 Status Displays, Generator in Standby
4.3 Controller Power
The DC2 controller is powered by the generator set engine starting battery.
Note: To disconnect controller power, disconnect the utility power to the generator set and disconnect the battery (negative lead first).
4.4 Battery Charging
The controller includes a
The installer must connect 120 VAC/60Hz utility power provided from the building on a
Section 4 DC2 Controller Operation 55 |