Warning (W) or

 

 

Fault

Shutdown (SD)

Condition

Check

 

 

 

 

Frequency High

SD *

Governed frequency exceeds 110% of the

Contact an authorized

 

 

system’s frequency setpoint for more than 10

distributor/dealer for service.

 

 

seconds. Function becomes active 10 seconds

 

 

 

after engine start (10 second inhibit).

 

 

 

 

 

Frequency Low

SD *

Governed frequency falls below 90% of the

Reduce the load and restart the

 

 

system frequency setting for more than

generator set.

 

 

10 seconds, or 1 Hz below the system frequency

Contact an authorized

 

 

setting for more than 60 seconds.

distributor/dealer for service.

 

 

Function becomes active 10 seconds after

 

 

 

 

 

engine start (10 second inhibit).

 

 

 

 

 

Lo Crank Vlt

W

Low cranking voltage. Battery voltage falls below

Charge or replace the battery.

 

 

8 VDC for more than 6 seconds while the starter

 

 

 

is engaged.

 

 

 

 

 

MainPwrOverL

SD

Main power overload. An over current fault on

Contact an authorized

 

 

the 70 controller power output (short circuit).

distributor/dealer for service.

 

 

 

Check for shorted run relay.

 

 

 

Check wiring for short circuits.

 

 

 

 

Not in Auto

W

The generator set is not in Automatic (standby)

Press AUTO to place the generator

 

 

mode. Remote start and stop commands from a

set in Automatic mode, when

 

 

transfer switch or remote switch will be ignored.

appropriate.

 

 

 

 

Oil Pres Low

SD *

The LOP switch indicates low oil pressure for

Check for leaks in the lubrication

 

 

more than 5 seconds. Function becomes active

system.

 

 

30 seconds after crank disconnect (30 second

Check the oil level and add oil if the

 

 

inhibit).

 

 

level is low.

 

 

Note: The low oil pressure shutdown does not

 

 

Check the oil pressure switch and

 

 

protect against low oil level. Check the engine oil

 

 

wiring

 

 

level regularly as recommended in Section 5.

 

Over Crank

SD

Three unsuccessful starting attempts.

Check the fuel supply, spark plug,

 

 

 

and battery.

 

 

 

Reset the thermostat.

 

 

 

Check for loose connections.

 

 

 

Contact an authorized

 

 

 

distributor/dealer for service.

Spd Sens Flt

SD

Engine speed sensor has failed or engine

Contact an authorized

 

 

stalled.

distributor/dealer for service.

 

 

 

 

Total Power

SD

Measured load is greater than 102% of the

Reduce the load.

High

 

generator set power rating for more than 1

 

 

 

minute (10RESV and 12RESV only).

 

 

 

 

 

Volts L1-L2

SD *

Generator voltage high. Output voltage exceeds

Contact an authorized

High

 

120% of the system nominal voltage for more

distributor/dealer for service.

 

 

than 2 seconds.

 

 

 

 

 

Volts L1-L2 Low

SD *

Generator voltage low. Output voltage falls

Reduce the load and restart the

 

 

below 80% of the nominal system voltage for

generator set.

 

 

more than 10 seconds.

Contact an authorized

 

 

 

 

 

 

distributor/dealer for service.

 

 

 

 

* Engine cooldown runs before shutting down.

 

Figure 2-3Controller Fault Messages

26 Section 2 Generator Set Operation

TP-6880 10/14

Page 26
Image 26
Kohler 8/10/12RESVL manual 3Controller Fault Messages, Fault Shutdown SD Condition Check