3.15 ATS Status Menu

ATS menus appear if a Model RXT transfer switch is connected to the generator set. If no transfer switch is connected, or another model ATS is connected to the engine start connections, Remote ATS is displayed on the ATS Status screen.

The ATS Status menu displays Model RXT transfer switch and source information.

The voltage shown in these menus can be calibrated. Follow the safety precautions at the beginning of this manuals. Use a voltmeter to measure the line-to-line voltage and follow the instructions in Figure 3-16 to calibrate the voltage readings.

ATS ---->

Status

 

Note: If there is no Model RXT transfer

 

switch connected to the generator set,

ATS Position:

Remote ATS is displayed and the other

Normal

screens on this page do not appear.

Normal Status:

Not/Acceptable

Emerg. Status:

 

Standby

Note: Sample data shown.

 

Single-phase

Three-phase

Normal Volts:

Normal Voltage:

240.0 V

L1--L2

240 V

Normal Freq.:

Normal Voltage:

60.0 Hz

L2--L3

240 V

Emerg Volts:

Normal Voltage:

240.0 V

L3--L1:

240 V

Emerg. Freq.:

Normal Freq.:

60.0 Hz

 

60.0 Hz

 

Normal Rotation:

 

 

Similar screens appear for

 

 

the emergency source.

Reset

Reset

 

Calibration

Calib? No

<---- Return

Reset

tp6810

Calib? Yes

 

Figure 3-16ATS Status Menu, with Calibration