5. PARAMETERS
No. Symbol Name and function Initial
value Unit Setting
range
PB18 LPF Low-pass filter setting
Set the low-pass filter.
Setting parameter No.PB23 (low-pass filter selection) to " 0 " automatically
changes this parameter.
When parameter No.PB23 is set to " 1 ", this parameter can be set manually.
3141 rad/s 100
to
18000
PB19 VRF1 Vibration suppression control vibration frequency setting
This parameter cannot be used in the speed control mode.
Set the vibration frequency for vibration suppression control to suppress low-frequency
machine vibration, such as enclosure vibration. (Refer to section 7.4.(4))
Setting parameter No.PB02 (vibration suppression control tuning mode) to " 1"
automatically changes this parameter. When parameter No.PB02 is set to " 2",
this parameter can be set manually.
100.0 Hz 0.1
to
100.0
PB20 VRF2 Vibration suppression control resonance frequency setting
This parameter cannot be used in the speed control mode.
Set the resonance frequency for vibration suppression control to suppress low-
frequency machine vibration, such as enclosure vibration. (Refer to section 7.4.(4))
Setting parameter No.PB02 (vibration suppression control tuning mode) to " 1"
automatically changes this parameter. When parameter No.PB02 is set to " 2",
this parameter can be set manually.
100.0 Hz 0.1
to
100.0
PB21 0.00
PB22
For manufacturer setting
Do not change this value by any means. 0.00
PB23 VFBF Low-pass filter selection
Select the low-pass filter.
Low-pass filter selection
0: Automatic setting
1: Manual setting (parameter No.PB18 setting)
00 0When automatic setting has been selected, select the filter that has the band width
close to the one calculated with VG2 10
1 + GD2 [rad/s]
0000h Refer to
Name
and
function
column.
PB24 *MVS Slight vibration suppression control selection
Select the slight vibration suppression control and PI-PID change.
When parameter No.PA08 (auto tuning mode) is set to " 3", this parameter is
made valid. (Slight vibration suppression control cannot be used in the speed control
mode.)
Slight vibration suppression control selection
0: Invalid
1: Valid
00
PI-PID control switch over selection
0: PI control is valid. (Switching to PID
control is possible with instructions of
controller.)
3: PID control is alwa
y
s valid.
0000h Refer to
Name
and
function
column.
PB25 For manufacturer setting
Do not change this value by any means.
0000h