13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
13.3.3 Terminal Refer to section 13.7 for the terminal block arrangement and signal layout. (1) Converter unit Description Connection target
(Application) Abbreviation (Note)
Terminal block MR-J3-CR55K MR-J3-CR55K4
Main circuit power supply L1L2L3 TE1-1
Connect 3-phase 200 to
230VAC, 50/60Hz to L1, L2, L3.
Connect 3-phase 380 to
480VAC, 50/60Hz to L1, L2, L3.
Control circuit power supply L11 L21 TE3
Connect 1-phase 200 to
230VAC, 50/60Hz.
Connect 1-phase 380 to
480VAC, 50/60Hz.
Power factor improving
DC reactor P1P2 TE1-2
When using the power factor improving DC reactor, connect it after
removing the connection plate across P1-P2.
Regenerative brake P2C TE1-2 Connec t to the P2 and C terminals of the regenerative option.
DC link L L TE2-2
Connect to the L , L terminals of the drive unit.
Use the connection bar, which is supplied with the drive unit, to
connect.
Grounding PE
Connect this terminal to the protective earth (PE) terminals of the
servo motor and control box for grounding.
Note. The permissible tension applied to any of the terminal blocks TE1-1, TE1-2, TE2-2 is 350[N].
(2) Drive unit Description
Connection target
(Application) Abbreviation (Note)
Terminal block MR-J3-DU30KB
MR-J3-DU37KB
MR-J3-DU30KB4 to
MR-J3-DU55KB4
Control circuit power supply L11 L21 TE3
Connect 1-phase 200 to
230VAC, 50/60Hz.
Connect 1-phase 380 to
480VAC, 50/60Hz.
LL power supply input L L TE2-1
Connect to the L and L terminals of the converter unit.
Use the connection bar, which is supplied with the drive unit, to
connect.
Servo motor power U VW TE1A Connect to the servo motor power terminals (U, V, W).
Grounding PE
Connect this terminal to the protective earth (PE) terminals of the
servo motor and control box for grounding.
Note. The permissible tension applied to any of the terminal blocks TE1, TE2-1 is 350[N].