3 - 6
3. SIGNALS AND WIRING
(5) MR-J3-500B MR-J3-700B
EM1
NFB MC
L1
L2
L3
ALM RA1
P1
DICOM
DOCOM
N
U
V
W
(Note 2)
(Note 1)
TE1
PE
U
V
W
2
3
4
1
M
Motor
Encoder
CN2
24VDC
(Note 3)
Encoder cable
(Note 6)
DOCOM
Forced stop
CN3CN3
OFF
Forced
stop ON
MC
MC
SK
(Note 4)
Alarm
RA1
Controller
forced stop
RA2
Servo amplifier Servo motor
(Note 5)
Trouble
(Note 4)
(Note 5)
3-phase
200 to
230VAC
L11
L21
TE2
P1
P2
N
TE3
Built-in
regenerative
resistor
Cooling fan
(Note 7)
Power supply
of Cooling fan
BU
BV
NFB

Note 1. Always connect P1 and P2. (Factory-wired.) When using the power factor improving DC reactor, refer to section 11.13.

2. When using the regenerative option, refer to section 11.2.

3. For the encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the c able.

4. If deactivating output of trouble (ALM) with parameter change, configure up the power supply circuit which switches off the

magnetic contactor after detection of alarm occurrence on the controller side.

5. For the sink I/O interface. For the source I/O interface, refer to section 3.7.3.

6. Refer to section 3.10.

7. A cooling fan is attached to the HA-LP601 and the HA-LP701M servo motors. For power supply specification of the cooling fan,

refer to section 3.10.2 (3) (b).