9600 Compressor Description

CTI-CRYOGENICS

HELIX TECHNOLOGY CORPORATION

Return Gas Coupling

The Return Gas Coupling returns the helium, which has been cycled through the cryopump, back to the Compressor. Refer to CTI-CRYOGENICS Helium Refrigeration System within this section for more information.

Cooling Water IN

The Cooling Water IN connector provides water to the Compressor from your facility to cool the Compressor during operation. The connector thread size is a 1/2 in. female pipe thread. The water must meet the specifications outlined in Table 1-3. Refer to Section 3 - Installation for more information on cooling water connections.

Cooling Water OUT

The Cooling Water OUT connector returns the water that has been used to cool the Compressor to your facility. The connector thread size is a

1/2 in. female pipe thread. Refer to Section 3 - Installation for more information on cooling water connections.

Cryopump Electrical Outlet

The Cryopump Electrical Outlet provide power to a single On-Board or Cryo-Torr Cryopump, an On-Board Splitter Box, or a Cryo-Torr Interface. The Compressor requires the use of an On-Board Splitter Box or Cryo-Torr Interface for multiple cryopump system connections. Refer to Table 1-5 for connector pin identification. Refer to Multiple On-Board Cryopump Connections or Multiple Cryo-Torr Cryopump Connections within this section for more information.

Table 1-5: Cryopump Electrical Outlet Pin Assignments

Identifier

Function

 

 

A and B

Heater Power - 208 VAC nominal

CCenter tap for D and E

D and E 24 VCT @ 4.6 Amps

F-G and G-H Cold Head Voltage Output 130-160 VAC @ 4.5 Amps

 

 

J

Chassis Ground

 

 

K

Not Used

1-10

P/N 8040540

Page 17
Image 17