EMC Cabling

For electromagnetic compatibility, you must use cables shown to be usable in EMC installations. Cables should have a minimum of 85% braid coverage, and be 360° bonded at both ends.

EMC Motor

For system CE compliance, you must use an EMC-ready motor, or a motor that has demonstrated acceptable EMC performance.

NOTE: Motors may bear the CE mark. This mark indicates the motor meets the requirements of construction and safety— not EMC compliance .

Motors with shielded cabling or pipe thread style cabling options allow the easiest integration into machines required to bear the CE mark for EMC.

Varistors

You must install varistors or other voltage surge limiting devices in order to meet the requirements of EN61000-4-5. Place a Littelfuse V140LA1Ø or equivalent varistor from line to line, and from lines to earth before the mains filter, as shown in the EMC Installation drawing later in this appendix. (Intersil, General Electric and Littelfuse manufacture equivalent varistors.)

Mains Filter

You must install a mains filter. The next table lists recommended filters.

 

Continuous

Filter:

Current (amps)

6EP11

6

10EP11, 3

10

FN2070-10-062

10

1Corcom; 2 Schaffner;

3Available from Compumotor: 10 amp filter – part number 47-016140-01

Installation Guidelines

The E-AC Drive is made available under “ Restricted Distribution” for use in the “ Second Environment” as described in EN 61800-3: 1996, page 9.

Cabinet Mounting

For Electromagnetic Compatibility, cabinet mounting is not required. However, the E-AC Drive has high voltage terminals— for safety purposes, the drive must not be user accessible during normal operation.

Drive Mounting

The E-AC Drive is designed to be mounted to an earthed metal panel. For EMC performance, mount the mains filter to the same panel, as close to the drive as possible. See the EMC Installation drawing at the end of this appendix.

Cable Routing

Route high power cables (motor and mains) at right angles to low power cables (communications and inputs/outputs). Never route high and low power cables parallel to each other.

E-AC Drive Hardware Installation Guide

Appendix B – Regulatory Compliance: UL and CE 43

Page 43
Image 43