Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
1.Main tubing length LM = LA + LB … ≤ 262 ft
2.Main distribution tubes LC – LG are selected according to the capacity after the distribution joint.
3. The outdoor connection main tubing (B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
4.Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.
H3
L5
B
L1
L2
LM
A
Balance tubing |
| LB | LC | LD | |
(ø1/4") | LA |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
L3
H1
Explanation of symbols |
| 4 |
|
| For |
Distribution joint | LE | extension |
Max. 1.3 ft |
| |
(APR: purchased separately) |
| |
| For | |
|
| |
|
| extension |
Ball valve (field supply) | Max. 1.3 ft | LG |
| ||
|
| |
|
| |
Solidly welded shut | LF | 1 |
|
| |
(pinch weld) | L4 |
|
|
|
5
2
38 | 39 |
3
40
H2
R410A distribution joint
Note: Do not use commercially available
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor unit connections and tubing branches.
Table
Item | Mark |
|
| L1 |
|
| ∆L (L2 – L4) |
|
Allowable tubing | LM |
|
length |
| |
1, 2... 40 |
| |
|
| |
| L1+ 1+ 2 ... 39 | + |
| A+LE+LF+LG | |
| L5 |
|
Allowable elevation | H1 |
|
|
| |
difference | H2 |
|
| H3 |
|
Allowable length of | L3 |
|
joint tubing |
| |
|
| |
L = Length, H = Height |
|
|
|
|
Contents
Actual length
Max. tubing length
Equivalent length
Difference between max. length and min. length from the No.1 distribution joint
Max. length of main tubing (at max. diameter)
Max. length of each distribution tube
Total max. tubing length including length of each distribution tube (only liquid tubing)
Distance between outdoor units
When outdoor unit is installed higher than indoor unit
When outdoor unit is installed lower than indoor unit
Max. difference between indoor units
Max. difference between outdoor units
Length (ft.)
> | 492 |
| |
> | 574 |
| |
> | 131 |
| |
> | 262 *3 |
> | 98 |
| |
> | 984 |
| |
> | 32 |
| |
> | 164 |
| |
> | 131 |
| |
> | 49 |
| |
> | 13 |
| |
> | 6.6 |
NOTE
1:The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
2:If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table
3:If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)
4:If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.
*If the existing tubing is used, and the amount of
Max. additional charge for 1 outdoor unit: 62 lbs
Max. additional charge for 2 outdoor units: 111lbs