Sanyo 85464359982001 installation instructions Straight Equivalent Length of Joints

Models: 85464359982001

1 96
Download 96 pages 22.69 Kb
Page 13
Image 13
1-7. Straight Equivalent Length of Joints

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 13

1-7. Straight Equivalent Length of Joints

Design the tubing system by referring to the following table for the straight equivalent length of joints.

Table 1-13 Straight Equivalent Length of Joints

 

 

 

 

 

 

 

Unit: ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas tubing size (in. (mm))

1/2"

5/8"

 

3/4"

7/8"

1"

1-1/8"

1-1/4"

1-1/2"

(12.7)

(15.88)

 

(19.05)

(22.22)

(25.4)

(28.58)

(31.8)

(38.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90° elbow

 

 

 

1

1.1

 

1.4

1.6

1.7

1.9

2.3

2.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45° elbow

0.8

0.9

 

1

1.2

1.3

1.4

1.7

1.9

 

 

 

 

 

 

 

 

 

 

 

 

 

U-shape tube bent (R2-3/8" – 4" (60 – 100))

3

3.4

 

4.1

4.7

5.1

5.6

6.9

7.8

 

 

 

 

 

 

 

 

 

 

 

 

 

Trap bend

7.5

9.2

 

10.5

12.5

14.1

15.4

16.4

14.0

 

 

 

 

 

 

 

 

 

 

 

 

 

Y-branch distribution joint

 

 

Equivalent length conversion not needed.

 

 

 

 

 

 

 

 

 

Ball valve for service

 

 

Equivalent length conversion not needed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1-14 Refrigerant tubing (Existing tubing can be used.)

Tubing size (in. (mm))

Material O

Material 1/2H • H

 

 

 

 

ø1/4" (ø6.35)

t1/32" (0.8)

ø7/8" (ø22.22)

t5/128" (1.0)

 

 

 

 

ø3/8" (ø9.52)

t1/32" (0.8)

ø1" (ø25.40)

t5/128" (1.0)

ø1/2" (ø12.7)

t1/32" (0.8)

ø1-1/8" (ø28.58)

t5/128" (1.0)

 

 

 

 

ø5/8" (ø15.88)

t5/128" (1.0)

ø1-1/4" (ø31.75)

t3/64" (1.1)

 

 

 

 

ø3/4" (ø19.05)

over t5/128" (1.0)

ø1-1/2" (ø38.10)

over t3/64" (1.15)

 

 

ø1-5/8" (ø41.28)

over t3/64" (1.20)

 

 

 

 

1-8. Additional Refrigerant Charge

*When bending the tubes, use a bending radius that is at least 4 times the outer diameter of the tubes.

In addition, take sufficient care to avoid crushing or damaging the tubes when bending them.

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 1-15 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

 

 

ø1/4" (ø6.35)

0.279

ø3/8" (ø9.52)

0.602

 

 

ø1/2" (ø12.7)

1.38

ø5/8" (ø15.88)

1.99

 

 

ø3/4" (ø19.05)

2.78

 

 

ø7/8" (ø22.22)

3.93

Required amount of charge = (Amount of refrigerant charge per meter of each size of liquid tube its tube length) + (...) + (...)

*Always charge accurately using a scale for weighing.

*If the existing tubing is used, and the amount of on-site additional

refrigerant charge exceeds the value listed below, then change the size of the tubing to reduce the amount of refrigerant.

Max. additional charge for 1 outdoor unit :62 lbs Max. additional charge for 2 outdoor units :111 lbs Max. additional charge for 3 outdoor units :133 lbs

Table 1-16 Refrigerant Charge Amount at Shipment (for outdoor unit)

DC

(oz)

CHDX09053

CHDX14053

 

 

423

458

 

 

1-9. System Limitations

Table 1-17 System Limitations

Max. No. allowable connected outdoor units

2 *1

 

 

Max. capacity allowable connected outdoor units

307,100 BTU/h (32 hp, 90 kW)

 

 

Max. connectable indoor units

40

 

 

Max. allowable indoor/outdoor capacity ratio

50 – 130 %

 

 

*1: Up to 2 units can be connected if the system has been extended.

13

Page 13
Image 13
Sanyo 85464359982001 installation instructions Straight Equivalent Length of Joints