07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 71

8-2. Test Run Procedure

Recheck the items to check before the test run.

Items to Check Before the Test Run

1.

Turn the remote power switch on at least 5 hours

 

before the test, in order to energize the crank

 

case heater.

2.

After performing the leak inspection, applying

 

vacuum, and performing refrigerant charge for

<Outdoor unit control PCB> Unit No. setting switch (S007)

<Outdoor unit control PCB> Unit No. setting switch (S006)

<Outdoor unit control PCB> Unit No. setting switch (S004 and S005)

(Check the link wiring.)

<Outdoor unit control PCB> Unit No. setting switch (S002 and S003)

NO

Have the outdoor sub units been connected?

YES

Set the unit address.

*1

 

 

 

 

 

 

 

 

Set the No. of outdoor units.

 

 

 

 

 

 

 

 

 

 

 

 

Set the No. of indoor units.

 

 

 

NO

 

 

Are the inter-unit control wires

connected to more than 1 refrigerant

 

system?

 

 

 

YES

 

 

 

 

Set the system address.

 

*1 The unit with the unit No. set to 1 is the main unit. All other units are sub units.

CASE 1

 

the tubing which is connected on-site, fully open

 

the outdoor unit service valve. However if only

 

one outdoor unit is installed, a balance tube is

 

not used. Therefore, leave the valve fully closed.

3.

When replacing the control PCB, be sure that

 

the settings on the new PCB match those on the

 

old PCB.

4.

Use caution when making the settings. If there

 

are duplicated system addresses, or if the

 

settings for the Nos. of the indoor units are not

 

consistent, an alarm will occur and the system

 

will not start.

5.

These settings are not made on the indoor unit

 

PCB.

When multiple outdoor main units exist, disconnect the terminals

Refer to Fig. 8-4extended from the shorted plugs (CN003) at all outdoor main unit PCBs except for 1.

Alternatively, move the sockets to the OPEN side.

Note: It is not necessary to remove the socket that is used to short-circuit the terminal plugs from the outdoor sub unit PCBs.

 

 

Is it possible to turn ON the power only

 

YES CASE 2

 

 

 

 

 

for the 1 refrigerant system where the

 

 

 

 

 

 

 

 

 

 

 

test run will be performed?

 

 

 

 

 

 

 

 

Turn ON the indoor and

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor unit power for that

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant system only.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Will automatic address setting be

 

 

 

Make necessary corrections.

 

 

 

 

 

 

 

 

Short-circuit the automatic address pin (CN100)

 

NO

performed in Heating mode?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on the outdoor main unit PCB for 1 second or

 

 

 

 

 

 

 

 

 

 

 

 

longer, then release it.

 

CASE 3B

 

YES

CASE 3A

Turn OFF the indoor and

 

 

 

 

 

 

 

 

 

outdoor unit power.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is it OK to start the compressors?

Is it OK to start the compressors?

 

 

 

 

 

 

 

LED 1 and 2 blink alternately

 

 

 

 

Check the alarm contents.

 

(about 2 or 3 minutes).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the indoor and

Turn ON the indoor and

 

 

 

 

 

 

NO

 

 

 

outdoor unit power.

outdoor unit power.

 

 

 

 

 

 

 

Are LEDs 1 and 2 on the

*2

 

*2

 

 

 

Make necessary

 

 

 

 

outdoor unit PCB OFF?

Short-circuit the mode change pin

Short-circuit the automatic address

 

corrections

 

Refer to “Table of

 

 

 

 

 

 

(CN101) on the outdoor main unit PCB.

pin (CN100) on the outdoor main

 

 

 

 

Self-Diagnostic Functions and

 

 

 

 

 

 

Description of Alarm Displays.”

 

YES

At the same time, short-circuit the

unit PCB for 1 second or longer,

 

 

 

 

 

Turn OFF the indoor and

 

 

 

 

automatic address pin (CN100) for 1

then release it.

 

 

outdoor unit power.

 

 

 

 

 

second or longer, then release it.

 

 

 

 

 

 

 

 

 

 

 

 

*3

 

*3

 

Start indoor and outdoor unit

Start indoor and outdoor unit

cooling operation.

 

heating operation.

LED 1 and 2 blink alternately.

LED 1 and 2 blink alternately.

 

 

NO

 

 

 

 

Are LEDs 1 and 2 on the

 

outdoor unit PCB OFF?

 

YES

Check the alarm

contents.

*2 A minimum of 5 hours must have passed after the power was turned ON to the outdoor unit.

*3 All indoor units operate in all refrigerant systems where the power is ON.

Check that test run preparation is OK.

(Do not allow the short-circuited pins to remain short-circuited.)

Set the wired remote controller for test run.

Refer to the remote

 

 

NO

 

 

controller test-run

 

 

Does system operate?

settings.

 

 

 

Check and make corrections according to “Table of Self-Diagnostic Functions.”

YES

Return remote control to normal mode

Fig. 8-3

End test run.

71

Page 71
Image 71
Sanyo 85464359982001 installation instructions Test Run Procedure, Items to Check Before the Test Run