Manuals
/
Sanyo
/
Household Appliance
/
Air Conditioner
Sanyo
85464359982001 Fig, Main Outdoor Unit PCB Setting, 07-007 W-2WAY II NA1/23/07 6 09 PM Page
Models:
85464359982001
1
72
96
96
Download
96 pages
22.69 Kb
69
70
71
72
73
74
75
76
<
>
Troubleshooting
Install
Wiring System Diagram
Dimension
Wiring the Ceiling Panel
Test Run Procedure
Alarm display
Adjusting the Auto Flap
Setting at time of
Care And Cleaning
Page 72
Image 72
07-007
W-2WAY_II_NA
1/23/07 6:09 PM Page 72
8-3.
Main Outdoor Unit PCB Setting
S003 S002 S004 S005 S006 S007
CN100
CN101
CN003
Fig.
8-4
72
Page 71
Page 73
Page 72
Image 72
Page 71
Page 73
Contents
X A U D T K
R410A Models Indoor Units
Outdoor Units
Optional Controllers
SPECIAL PRECAUTIONS
ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM
…In a Room
…In Moist or Uneven Locations
Check of Density Limit
1. Care regarding tubing
3. Different tools required
Manifold gauge Vacuum pump
1. Compressor specifications are different
Single-outletvalve
2. Existing tubing cannot be used especially R22
R410A
CONTENTS
3.HOW TO INSTALL THE INDOOR UNIT
4-WayAir Discharge Semi-ConcealedType X Type
1-WayAir Discharge Semi-ConcealedType A Type
6. HOW TO PROCESS TUBING . . . . . . . . . . . .
1. GENERAL
1-1.Tools Required for Installation not supplied
1-2.Accessories Supplied
Refer to “5. ELECTRICAL WIRING” for details
Table 1-2 4-WayAir Discharge Semi-Concealed
Table 1-3 1-WayAir Discharge Semi-Concealed
Table 1-4Concealed Duct
Part Name
Table 1-5Concealed Duct High-StaticPressure
Table 1-6 Ceiling-Mounted
Table 1-7 Wall-Mounted
Part Name
Allowable tubing
length
1, 2...
L1+ 1+ 2 ...
Size of tubing LO between outdoor units
1-7.Straight Equivalent Length of Joints
unit is installed 1-10.Check of Limit Density
1-12.Optional Distribution Joint Kits
Model name
Cooling capacity after distribution
Remarks
Table 1-21Size of connection point on each part Shown are inside diameters of tubing
232,000 BTU/h 68.0 kW
460,700 BTU/h 135.0 kW
Additional refrigerant charging
the room in which the indoor unit is installed
Minimum room volume for indoor unit: ft.3
Main tubing
Distribution joint tubing
2. SELECTING THE INSTALLATION SITE
Ceiling-MountedType
1-WayAir Discharge Semi-ConcealedType
Wall-MountedType
2-2.Outdoor Unit AVOID
Top view
2-3.Shield for Horizontal Exhaust Discharge
2-6.Dimensions of Wind Ducting
2-unitinstallation
2-7.Dimensions of Snow Ducting
3.HOW TO INSTALL THE INDOOR UNIT
3-2.Suspending the Indoor Unit
Table
Fig.
3-4.Installing the Drain Piping
Tighten the hose clamps so
their locking nuts face upward
Fig.
start when you short the pin
3-5.Checking the Drainage
Be careful since the fan will
on the indoor control board
3-6.How to Install the Ceiling Panel
Removing the corner cover
Fig.
Fig.
3-6-2.Installing the Ceiling Panel
Fig.
Fig.
Fig.
3-6-3.Wiring the Ceiling Panel
3-6-4.How to Attach the Corner & Air-IntakeGrille
Attaching the corner cover and air-intakegrille
Fig.
3-6-5.Checking After Installation
3-6-7.Adjusting the Auto Flap
3-7.Special Remarks DC Fan Tap Change Procedure
Fig.
Fig.
3-9.Placing the Unit Inside the Ceiling
Fig.
Fig.
Fig.
3-10.Installing the Drain Piping
Fig.
Fig.
Fig.
Do not use natural drainage
3-11.Checking the Drainage
Fig.
Fig.
3-12.Electrical Power Wiring 1 Wiring connections
2 Wiring
3-13.How to Install the Ceiling Panel
3-13-1.Before Installing the Ceiling Panel
Fig. 3-13-2.Installing the ceiling panel
Removing the intake grille
Removing the side panel
Fig. 3-49a
Fig.
Fig.
Must be no gap Indoor unit
3-13-3.Wiring the ceiling panel
A. Installing the side panel
B. Installing the intake grille
3-13-5.Other A. Check after installation
Concealed Duct Type U Type
Table
Fig.
Table
3-15.Suspending the Indoor Unit
Fig.
Fig.
Fig.
3-16.Installing the Drain Piping
indoor unit
The maximum permissible bend is
3-17.Checking the Drainage
Be careful since the fan will start when you
How to read the diagram
short the pin on the indoor control board
3-18.Increasing the Fan Speed
Table
Concealed Duct High-StaticPressure Type D Type
Fig.
Fig.
enough to suport the weight of the unit
3-20.Suspending the Indoor Unit
It is important that you use extreme care
in supporting the indoor unit inside the
3-21.Installing the Drain Piping
How to Read the Diagram
3-22.Caution for Ducting Work
3-23.Indoor Fan Performance
3-24.Required Minimum Space for Installation and
Service
2 Refrigerant tubing • drain hose position
Ceiling-MountedType T Type
weight of the unit. Before
4 Wall and ceiling side opening position
Fig. 3-25.Suspending the Indoor Unit
It is important that you use
Fig. Fig.
Fig.
Fig.
Fig.
Fig. 3-28.Installing the Drain Piping
3-26.Duct for Fresh Air
3-27.Shaping the Tubing
Fig.
THow to carry out power supply wiring
When removing the fastening
and regulations before wiring
bracket from the cover of the
3-29.Removing the Rear Panel from the Unit
3-30.Selecting and Making a Hole
Wall-MountedType K Type
Fig.
b If the Wall is Brick, Concrete or Similar
Removing the grille
Attaching the grille
3-33.Preparing the Tubing
3-35.Installing the Drain Hose
3-34.Shaping the Tubing Right-reartubing
Left or left-reartubing
unit are completed
KHX0752 / 0952 / 1252 /
KHX2452
Setting at time of factory shipment
Setting at time of
4. HOW TO INSTALL THE OUTDOOR UNIT
4-2.Installing the Outdoor Unit
4-1.Transporting
Fig.
4-3.Routing the Tubing
Fig.
Fig.
4-4.Prepare the Tubing
Refrigerant tubing Existing tubing can be used
Tubing size in. mm
Material O
Refrigerant tube port
Tightening torque for each cap
0905 Type
1405 Type
5. ELECTRICAL WIRING
AWG #8
64 ft
60 A
5-3.Wiring System Diagram
K Type
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
How to connect wiring to the terminal
Shielded wire GroundGround
6. HOW TO PROCESS TUBING
6-1.Connecting the Refrigerant Tubing
Flaring Procedure with a Flare Tool
Use of the Flaring Method
ø1/4 ø6.35 mm
120 – 160 lbs · inch
1/32
140 – 180 kgf · cm
Two tubes arranged together
Three tubes arranged together
6-5.Finishing the Installation
6-4.Taping the Tubes
Fig.
Fig.
Manifold gauge
Vacuum pump
when 30 gal/h vacuum pump is used
Evacuation
Required time for evacuation
45 min. or more
R410A
Use a cylinder designed for use
with R410A respectively
Charging additional refrigerant
8. TEST RUN
8-1.Preparing for Test Run
Fig.
Fig.
8-2.Test Run Procedure
Items to Check Before the Test Run
8-3.Main Outdoor Unit PCB Setting
Fig.
S003 S002 S004 S005 S006 S007 CN100 CN101 CN003
07-007 W-2WAY II NA1/23/07 6 09 PM Page
Indoor unit setting S005
3 units, and set the unit No. DIP switch S007 to
Fig.
1-10
unit No.
Basic wiring diagram: Example
1-13
2-22-9
Fig.
Automatic Address Setting from Outdoor Unit
1. On the No
On the No
On the No.
Automatic Address Setting in Heating Mode
Automatic Address Setting from Outdoor Unit
Case 3A
Case
Automatic Address Setting in Cooling Mode
Automatic Address Setting from Outdoor Unit
Case 3B
Case
Display during automatic address setting
Remote controller display
On outdoor main unit PCB
LED 1 is D72. LED 2 is D75
8-5.Remote Controller Test Run Settings
Checking the indoor unit addresses
8-6.Caution for Pump Down
Alarm display
M = 2: P alarm
3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No
Alarm
Continued
Activation of
Alarm messages displayed on system controller
CARE AND CLEANING
9. APPENDIX
9-1. 4-WayAir Discharge Semi-ConcealedType X Type
NAME OF PARTS
TROUBLESHOOTING
Tips for Energy Saving
9-2. 1-WayAir Discharge Semi-ConcealedType A Type
CARE AND CLEANING
NAME OF PARTS
TROUBLESHOOTING
Tips for Energy Saving
Outdoor unit
CARE AND CLEANING
NAME OF PARTS
TROUBLESHOOTING
Should the power fail while the unit is running
Tips for Energy Saving
Avoid Do
9-4. Ceiling-MountedType T Type
CARE AND CLEANING
NAME OF PARTS
TROUBLESHOOTING
Tips for Energy Saving
or soot
9-5. Wall-MountedType K Type NAME OF PARTS
CARE AND CLEANING
TROUBLESHOOTING
or soot