Display during automatic address setting
●On outdoor main unit PCB
LED 2 1 | * Do not |
| ting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn |
Blink alternately | OFF. |
|
*When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.
*LED 1 is D72. LED 2 is D75.
*If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then perform automatic address setting again.
●Display details of LEDs 1 and 2 on the outdoor unit control PCB
( : ON | : Blinking | : OFF) |
LED 1 | LED 2 | Display meaning |
After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor units in that system is possible.
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are confirmed in that system; however, the number of indoor units does not match the number that was set.
Automatic address setting is in progress.
Alternating
Automatic address setting completed.
| At time of automatic address setting, the number of indoor units did not match the number that was set. |
Simultaneous | “ ” (when indoor units are operating) indication appears on the display. |
Alternating
Refer to “Table of
Note: “” indicates that the solenoid is fused or that there is a CT detection current failure (current is detected when the compressor is OFF).
●Remote controller display
is blinking
79